Permit Number: TC-COM-0925-01652
Parcel: 11901067J

Address:
3355 S 6TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0925-01652
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/10/2025 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0925-01652 (3355 S 6TH AV TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Provide Electrical load calculations which demonstrate that the premises electrical system has load capacity to accommodate the EV charging load (Include the EV charger in the load calculations as a continuous use item 625.41). NEC 625.42