Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0925-01641
Parcel: 14109030A

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0925-01641
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2025 Commercial Electrical Express APPROVED
09/11/2025 Commercial Mechanical Express APPROVED
09/11/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/11/2025 Commercial Plumbing Express REQUIRES RESUBMIT Based on the demand of 22.5 GPM, the existing 5/8” water meter is not sufficient. The Maximum Meter Design Capacity for a 5/8” meter is 20 GPM. A 3/4” water meter will be required.
09/08/2025 PDSD Application Completeness Express REVIEW COMPLETED