Permit Number: TC-COM-0925-01634
Parcel: 14118602A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0925-01634
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2025 Commercial Building Standard APPROVED Building(B) Reviewer (from previous submittal TUC9732001.090525)
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 9/11/2025 1:52:14 PM


Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 10/23/2025 8:46:50 AM
10/29/2025 Commercial Mechanical Standard APPROVED Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 10/23/2025 4:26:13 PM
11/05/2025 Outdoor Lighting Standard APPROVED Outdoor Lighting Code Reviewed and Approved on TC-COM-0925-01779. Any modifications to the building lighting for TC-COM-0925-01634 must include an updated Outdoor Lighting Calculation.
11/05/2025 Site Engineering Standard APPROVED
11/05/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/29/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 10/22/2025 10:31:51 AM
10-22-2025
Copy to clipboard
1. E702 LIGHTING AND EQUIPMENT SCHEDULES: Need to provide an interior lighting Comcheck to show IECC
compliance (cover sheet showing power used and ‘Passes’ is sufficient as required controls are shown on
plans). Addressed with Tucson Energy Compliance report.
2. E900 ENERGY COMPLIANCE CERTIFICATE - EXTERIOR LIGHTING: Tucson requires their own Tucson exterior
lighting calculation (Table 401) , which is a lumens per acre calculation which also calls out for full cut off fixtures.
Please consult Tucson’s city website: Outdoor Lighting Codes in Pima County . Not Addressed with included sheets
E1.1 and E1.2. The photometrics and calculations shown on these two sheets provided for reference specifically
exclude the area in question.
10/29/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 10/28/2025 11:29:30 PM
Second Plumbing Review: comments 1,4,8 Remain
Unresolved-1). Plan Page P101 Meat/Produce Coolers Plumbing Note#6: Missing detail on plan pages P400 or P401 that
correlates to Note # 6 on Plan page P101. Add detail on plan pages P400 or P401 that correlates to Note # 6 on Plan page
P101 to compliance with -2018 IPC 802.1.2 **Also if the is an indirect waste receptor outside of the coolers they need to be
indicated on the P101** (This is an walkin refrigerator as stated in that code section provided detail that correlates with the
correct note#6)
Resolved-2). Plan Page P00: Plan page is missing. Add missing plan page P000 -2018 IPC 106.3.1
Resolved-3). Plumbing Plans General: Missing Grease Interceptor sizing calculations. Add Grease interceptor Sizing
Calculations. -2018 Tucson Plumbing Code Amendments.
Unresolved-4). Plumbing Plans General: Missing Backflow device schedule with types & locations. Add Backflow device
schedule with types & locations.. -2018 IPC 608.1, 608.3
Resolved-5). Plan Page P300 or A900: Missing Scupper sizing Calculations. Add scupper Sizing calculations. -2018 IPC
1106.1, 1106.5, 1108
Resolved-6). Plan Page P500: Meat Prep Hand Sink drain piping missing for riser diagram. Add Meat Prep Hand Sink drain
piping to riser diagram. -2018 IPC 106.3.1
Resolved-7). Plan pages P000 or P001: Missing water piping sizing calculations. Add water piping sizing calculations. -2018
IPC 604.1, 604.3
8). New Comment. Plan Page P00: Now that grease interceptor calcs have been provided. To many devices connected to
the Hydro Mech Grease Trap. Per Tucson Plumbing Code Amendments no more than 4 devices and or a dishwasher can
connect to a hydro mech grease interceptor. GB-250 | Indoor/Outdoor Hydromechanical Grease Interceptor
10/21/2025 PDSD Application Completeness Express REVIEW COMPLETED