Permit Number: TC-COM-0925-01634
Parcel: 14118602A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0925-01634
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2025 Site Zoning Standard APPROVED
09/25/2025 Water - PDSD Standard APPROVED
10/08/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/22/2025 Commercial Building Standard REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 9/17/2025 6:27:59 PM
1. General / Geotechnical Report: Please provide a copy of the site-specific geotechnical report for this project. The
report should support the appropriateness of the selected foundation system for the project site. All submitted
geotechnical reports must be dated no later than three years from the submittal date. Outdated reports must be
accompanied by a letter from a qualified geotechnical engineer stating that the report requirements are still valid, or
stating what items may have changed. All building code references must be updated to the current code adopted by
the City.


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 9/11/2025 1:52:14 PM
09/22/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 9/10/2025 11:10:19 AM
1. E702 LIGHTING AND EQUIPMENT SCHEDULES: Need to provide an interior lighting Comcheck to show IECC
compliance (cover sheet showing power used and ‘Passes’ is sufficient as required controls are shown on plans).
2. E900 ENERGY COMPLIANCE CERTIFICATE - EXTERIOR LIGHTING: Tucson requires their own Tucson exterior
lighting calculation (Table 401) , which is a lumens per acre calculation which also calls out for full cut off fixtures.
Please consult Tucson’s city website: Outdoor Lighting Codes in Pima County .
09/22/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 9/17/2025 2:48:50 PM
1. General - Provide COMcheck Mechanical Compliance Certificate. Any other APPROVED certifying agency is
acceptable. - 2018 IECC Section C403.3.2 HVAC equipment performance requirements
09/22/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 9/21/2025 1:31:35 PM
First Plumbing Review:
1). Plan Page P101 Meat/Produce Coolers Plumbing Note#6: Missing detail on plan pages P400 or P401 that correlates to
Note # 6 on Plan page P101. Add detail on plan pages P400 or P401 that correlates to Note # 6 on Plan page P101 to
compliance with -2018 IPC 802.1.2 **Also if the is an indirect waste receptor outside of the coolers they need to be indicated
on the P101**
2). Plan Page P00: Plan page is missing. Add missing plan page P000 -2018 IPC 106.3.1
3). Plumbing Plans General: Missing Grease Interceptor sizing calculations. Add Grease interceptor Sizing Calculations. -
2018 Tucson Plumbing Code Amendments.
4). Plumbing Plans General: Missing Backflow device schedule with types & locations. Add Backflow device schedule with
types & locations.. -2018 IPC 608.1, 608.3
5). Plan Page P300 or A900: Missing Scupper sizing Calculations. Add scupper Sizing calculations. -2018 IPC 1106.1,
1106.5, 1108
6). Plan Page P500: Meat Prep Hand Sink drain piping missing for riser diagram. Add Meat Prep Hand Sink drain piping to
riser diagram. -2018 IPC 106.3.1
7). Plan pages P000 or P001: Missing water piping sizing calculations. Add water piping sizing calculations. -2018 IPC 604.1,
604.3
09/23/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0925-01634 (10000 E OLD VAIL RD TUCSON, AZ 85747)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
This will require all exterior lights to be shown on the site exterior lighting plan, including site and parking lot lights, and lights for other buildings as covered by the associated Development Package.
2. List the Lighting Area per OLC (E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
3. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
4. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
5. Show lamps with a maximum of 3500K color temperature, OLC 402.1. Multiple exterior lighting fixtures are shown with a CCT greater than the max allowed.
6. Fixtures installed under canopies and overhangs. Outdoor lighting fixtures shall not be counted in determining the total light output when they are full cutoff light fixtures installed under canopies, building overhangs, or roof eaves, OLC 401.2.1(3).
7. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

8. Specify any exceptions used.

9. Provide Curfew lighting controls If applicable Per section 403.



Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
09/29/2025 Site Engineering Standard REQUIRES RESUBMIT TC-COM-0925-01634
10000 E OLD VAIL RD

Site Engineering Comments are as follows:

1. This commercial building permit cannot be approved until the development package, TD-DEV-0725-00181, is approved by all reviewers. Please see that the comments left by the building reviewers are addressed, as well. UDC Article 3.3.3.7

Ryan Insalaco
Engineering Associate
ryan.insalaco@tucsonaz.gov
09/26/2025 Fire New Construction Standard REVIEW COMPLETED
09/05/2025 PDSD Application Completeness Express REVIEW COMPLETED