09/04/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/04/2025 Addressing Validation REQUIRES RESUBMIT Site plan missing complete project address. Resubmit site plan with complete project address.
09/04/2025 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0925-01624 (730 E GLENN ST TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

Notate the COT adopted code on the plan-set.

1. Notate on the plans if any additional loads are being added to the service.
2. Provide a complete line diagram, NEC 110.2, 2018 IBC 107.1.

3. Provide an electrical riser diagram, 2017 NEC 230.9. Notate the grounding and bonding method, 2017 NEC 250.20(B), 250.24, 250.30(A)(4). Metallic gas lines must be bonded and not be used as the primary grounding method, 2017 NEC 250.50, 250.52(B)(1).


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
09/04/2025 PDSD Application Completeness Express REVIEW COMPLETED