Permit Number: TC-COM-0925-01620
Parcel: 123100280

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0925-01620
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/01/2025 Site Zoning Standard APPROVED
09/17/2025 Commercial Electrical Standard NOT REQUIRED No modifications to the Electrical.
09/25/2025 Fire New Construction Standard NOT REQUIRED
09/16/2025 Site Engineering Standard NOT REQUIRED
09/26/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please provide the approval agency listing report numbers, or the full reports (such as ICC-ES, IAPMO, or other recognized agencies), for the Sikalastic-726 One Shot system with the next submittal. IBC Section 107.2.1
2. Please explain how wall termination/flashing detail 4/A104 is intended to allow the EIFS system to properly drain any water that may penetrate behind it. Based on the drawing, the flashing appears to extend above the bottom edge of the EIFS, which raises concerns about drainage continuity.
Per IBC Section 107.2.1, construction documents are required to clearly demonstrate code compliance. Could you clarify how this detail addresses drainage requirements for the EIFS system?
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
09/04/2025 PDSD Application Completeness Express REVIEW COMPLETED