Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2024 Commercial Mechanical APPROVED
10/31/2024 Commercial Plumbing APPROVED
10/11/2024 Commercial Structural APPROVED
10/30/2024 Site Engineering APPROVED
10/29/2024 Site Zoning APPROVED
10/31/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/29/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Classify all areas in the electrical power and lighting plans as required per NEC art 511.3.

2 Verify GFI protection as required per NEC art 511.12.

3 Provide complete compliance with the 2012 City of Tucson Outdoor Lighting Code (OLC). See section 104 for exterior lighting plan submittal requirements.

Ref 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code (OLC).