Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0924-01779
Parcel: 10706035A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0924-01779
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/25/2024 Commercial Electrical APPROVED
11/25/2024 Site Engineering APPROVED
12/06/2024 Site Zoning APPROVED
12/06/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
11/19/2024 Commercial Structural REQUIRES RESUBMIT 1. Thank You for responding to the required fire rating of the walls & roof against the side property line. However, the drawings are required to be made clearer as to where this would be required. Any walls (front/side/rear) and roof that falls within 5 ft from the side property line must have a fire rating of 1 hour. Please add notes to your drawings making it clear as to where this fire rating is to be applied per IBC Table 602.
2. You have confirmed the new addition as an S-2 occupancy classification. With that confirmed, a 2 hour fire rated wall is required between the Assembly and Service of trailers structure with occupancy classification of F-1 and the new S-2 Addition. Please make the necessary correction to the drawings to make this clear per IBC Table 508.4.
11/22/2024 Fire New Construction REQUIRES RESUBMIT Resolve all building comments.
Questions: patricia.shelton@tucsonaz.gov
11/12/2024 PDSD Application Completeness REVIEW COMPLETED