Permit Number: TC-COM-0924-01779
Parcel: 10706035A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0924-01779
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2024 Commercial Mechanical NOT REQUIRED
10/14/2024 Commercial Plumbing NOT REQUIRED
10/15/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
10/09/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide complete compliance with the 2018 IECC for the lighting.

2 Verify that exterior lighting luminaires lamp color temperature output does not exceed 3500K. OLC 402.1.

3 Electrical Plan sheets E1.1, E3, and E4.0 are missing from the plan set. See cover sheet ‘SHEET SCHEDULE’.

Ref; 2018 IBC section 107.2.1, 2017 NEC 2019 IECC, 2012 City of Tucson Outdoor Lighting Code (OLC).
10/14/2024 Commercial Structural REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0924-01779
ADDRESS/PARCEL: (1315 W MIRACLE MILE TUCSON, AZ 85705)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
COMMENTS:
1. The New Area is labeled as Storage Building. Should the Occupancy type be S-1?
2. A weep screed with a minimum vertical attachment flange of 3 1/2 inches shall be provided at or below the foundation plate line on exterior stud walls. The weep screed shall be placed not less than 4 inches above the earth or 2 inches above paved areas. The water-resistive barrier shall lap the attachment flange. The exterior lath shall cover and terminate on the attachment flange of the weep screed per IBC 2512.1.2 Weep Screeds. Where landings, aprons are located at same level as floor slab, provide concrete or CMU foundation curb or other approved means to achieve minimum 2 inch clearance between slab and stucco weep screed. On either side of the man doors and rollup door, you will not meet the clearance requirements for the weep screed unless you provide a curb as mentioned above. Please provide the detail drawings that comply to the building code.
3. Section 4/S3.1: please provide the proper counter flashing at metal deck flashing detail drawing.
4. Registrant seal/signature/date signed are missing for sheets CVR and SD-1.
5. Windows and door information are absent. Please provide information such as the SHGC, U values, sizes, double pane glazing?, etc.
6. Where fire separation distance is 5 ft or less, Provide 2 hour fire-resistance-rated construction on the roof and the exterior walls that are within 5 ft where 3 ft setback is shown on the drawing per IBC Table 602.
7. Please re-submit.
10/15/2024 Fire New Construction REQUIRES RESUBMIT Resolve all building comments.
john.vincent@tucsonaz.gov
5203495581
10/15/2024 Site Engineering REQUIRES RESUBMIT 1. The associated development package TD-DEV-0424-00126 must be approved before this building permit can be approved.

Mike Ortiz
michael.ortiz@tucsonaz.gov
10/11/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0924-01779
1315 W MIRACLE MILE. – C-2
STORAGE/WAREHOUSE ADDITION (1st Review)

TRANSMITTAL DATE: October 11, 2024

Resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Vehicle Rental and Sales, is a allowed use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 9.9.G.1& .2.

1. Zoning has reviewed the building plans for compliance with development package (DP) TD-DEV-0424-00126 and although it appears that they plans match unit the DP is approved by all review agencies Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
09/16/2024 PDSD Application Completeness REVIEW COMPLETED