Permit Number: TC-COM-0924-01769
Parcel: 132191530

Address:
2140 E AJO WY

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0924-01769
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2024 Fire New Construction NOT REQUIRED
10/01/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
09/30/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter to address each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
1. Please provide structural calculations, prepared by an Arizona licensed design professional used in the design of this project, to include the Equipment concrete pad / anchorage calculations. IBC 107.2.7
2. Please amend plans to provide a statement of special inspections and provide a list of the required special inspections on the plans IBC 1704, 107.2.1

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
10/01/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

Provide evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.

1. Provide site lighting plans with the following information on the plans;

(a) Provide a complete luminaire schedule.

(b) Full compliance with sections 104.2.1(1), (2), (3).

2 See table 401.1, Include parcel size, lighting area and option, and indicate this information in the lighting site plan.

3 402.1 (light source color temperature requirements, 3500K), shielding requirements, etc .

4 Provide calculations for total lumens allowed and total lumens proposed per acre for Full Cut Off and Unshielded per table 401.1.Must include existing to remain lighting.

5 Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

6 Specify any exceptions used.

7 Provide Curfew lighting controls If applicable Per section 403.

8 Provide complete compliance with the 2018 IECC for the interior and exterior lighting where applicable.

9 Do not confuse the Outdoor Lighting Code with the IECC.

10 Please provide manufacture cut sheets for all EV charging equipment specifications to allow the plan reviewer to verify the equipment complies with NEC art 625 requirements.

11 Provide more detail as to how the Charging Posts are protected from possible vehicle damage.

Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. 2018 IECC.
09/30/2024 Site Engineering REQUIRES RESUBMIT TD-DEV-0924-00254 must be approved before this building permit can be approved.

Mike Ortiz
michael.ortiz@tucsonaz.gov
09/30/2024 Site Zoning REQUIRES RESUBMIT FROM:
Fernando Garcia
PDSD Zoning Review Section

PROJECT:
TD-DEV-0924-00254
2130 E Ajo Wy, Tucson, AZ 85713
Commercial Building

TRANSMITTAL DATE: September 30, 2024

This building permit is submitted per development package permit TD-DEV-0924-00254. The development package (DP) must be approved before this building permit can be. Ensure that any changes made to the DP during its review process are made to these associated building plans.

If you have any questions about this transmittal, contact Fernando Garcia at fernando.garcia2@tucsonaz.gov.
09/16/2024 PDSD Application Completeness REVIEW COMPLETED