Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2023 Site Engineering APPROVED
12/01/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/22/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: TC-COM-0923-02247
8535 E SPEEDWAY BL Zoning C-1
Tractor Supply Company

TRANSMITTAL DATE:‎November 22, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Clarify why there is a difference square footage on the Development plan (38,869 SF) and the Building Plan (38,900 SF)




If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
11/27/2023 Water - PDSD REQUIRES RESUBMIT The 11/3/23 submittal did not include the civil plans showing the installation of the water service to the building. [Initial comment: Provide the civil plans showing the installation of the water service to the building and the installation of the building sewer as part of the building plan set. An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). Reference: Sections 107.2.1 and 107.2.6, IBC 2018.]
11/15/2023 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 10/3/2023 3:09:11 PM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 11/13/2023 11:36:45 AM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 10/3/2023 7:33:35 PM




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 10/5/2023 7:21:50 PM
Electrical Review of TSC
By: Ron Ross PE

E1.0: Accepted exterior lighting Comcheck instead of Tucson’s exterior Lumens calculation.

E2.0: Could not locate Plan Notes 22, 36, and 53.

E4.0: Riser Note 5 not used.

E5.0: Could not locate Keynotes 5 and 9.




Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved with Comments
Reason:
Date Completed : 11/12/2023 8:12:44 AM
Second Plumbing Review:OK Subject to Field Inspections
1). Resolved-Add down spout & scupper sizing calculations to plan page A7.0 -IPC 1106.1, 1106.3, 1106.5

2). Resolved-Keynote#3 information not listed on plan page P1.0 -IPC 106.3.1
3). Resolved-Plan pages P1.0 & P1.1 need to include Shut off valves at each hose bib -IPC 606.2

4). Resolved-Trench Drains & floor drains In greenhouse area on plan pages P1.0 & P1.1 need to discharge thru an Sand interceptor -IPC 1003.1, 1003.5

5). Resolved- Trench Drains & trench drain's separate Building Drain Needs to be vented to the the exterior. -IPC 901.2.1, 904.1
11/07/2023 PDSD Application Completeness Express REVIEW COMPLETED