Permit Number: TC-COM-0923-02247
Parcel: 133100210

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0923-02247
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/06/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 10/3/2023 3:09:11 PM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 10/3/2023 3:09:05 PM
1. General: Roof drainage sizing calculations have not been provided. Provide roof drain sizing calculations to the roof plan in accordance with 2018 IPC Section 1106.1 & 1106.2

2. General: GPM discharge amounts have not been provided for the roof/drain overflows. Provide the roof/drain overflows in accordance with 2018 IPC Section 1106.2

3. General: It appears that the numbers of bathrooms provided are not sufficient. Provide detailed plumbing fixture calculations.



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 10/3/2023 7:33:35 PM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 10/5/2023 7:21:50 PM
Electrical Review of TSC
By: Ron Ross PE

E1.0: Accepted exterior lighting Comcheck instead of Tucson’s exterior Lumens calculation.

E2.0: Could not locate Plan Notes 22, 36, and 53.

E4.0: Riser Note 5 not used.

E5.0: Could not locate Keynotes 5 and 9.




Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 10/6/2023 7:07:16 PM
First Plumbing Review:
1). Add down spout & scupper sizing calculations to plan page A7.0 -IPC 1106.1, 1106.3, 1106.5

2). Keynote#3 information not listed on plan page P1.0 -IPC 106.3.1

3). Plan pages P1.0 & P1.1 need to include Shut off valves at each hose bib -IPC 606.2

4). Trench Drains & floor drains In greenhouse area on plan pages P1.0 & P1.1 need to discharge thru an Sand interceptor - IPC 1003.1, 1003.5 or Provide letter from Utility authority stating not required

5). Trench Drains & trench drain's separate Building Drain Needs to be vented to the the exterior. -IPC 901.2.1, 904.1
10/18/2023 Site Engineering REQUIRES RESUBMIT See zoning comment
10/13/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0923-02247
8535 E. Speedway Bl. - C-1
Tractor Supply Company (1st Review)

TRANSMITTAL DATE: October 13, 2023

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-1 zone (UDC 4.7.20). General Merchandise Sales is a permitted use in this zone (Table 4.8-4), subject to Use Specific Standards 4.9.9.B.3 and 4.9.13.O.

1. COMMENT: Zoning has reviewed the building plans for compliance with Development Package (DP) TD-DEV-0623-00286 and all though it appears that the plans match, until the DP is approved by all review agencies Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
10/23/2023 Water - PDSD REQUIRES RESUBMIT Provide the civil plans showing the installation of the water service to the building and the installation of the building sewer as part of the building plan set. An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). Reference: Sections 107.2.1 and 107.2.6, IBC 2018.
10/17/2023 Fire New Construction REVIEW COMPLETED
09/21/2023 PDSD Application Completeness Express REVIEW COMPLETED