Permit Number: TC-COM-0923-02246
Parcel: 14036349A

Review Status: Requires Resubmit

Review Details: RESTAMP - COMMERCIAL v.1

Permit Number - TC-COM-0923-02246
Review Name: RESTAMP - COMMERCIAL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/29/2024 Site Engineering APPROVED
03/06/2024 Water - PDSD APPROVED
03/06/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
03/05/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 1/18/2024 7:10:46 PM
Second Plumbing Review: MEP response letter not attached as stated
Unresolved-1). Water piping & water piping fittings on plan page P1.3 are not compatible. & doesn't correlate with water
piping materials on plan page P1.2 -IPC 605
Unresolved-2). Carwash water connection on plan page P1..2 needs RPZ Backflow preventer. -IPC 608 ** the RPZ needs to
be located on branch supplying car wash**
Resolved-3). Storm drain calculation table on P1.1 is using the incorrect rainfall rate -Tucson Plumbing Code Amendments.
Unresolved-4). Horizontal portion of 3" roof drain conductors on P1.1 will need 1/4" slope -IPC 1106.2
Unresolved-5)., Plumbing plan & floor plan not clear where the 2 washing machines are located and where they connects to
the sanitary & water piping systems. They will need to discharge thru a lint interceptor. - IPC 106.3.1, 1003.6 ( 2 clothes
washers are listed on plan page P1.1 Waste water calculations)
Resolved-6). Plan set missing Pages C4.1, 4.2, 4.3 for continuation of water service & sewer as stated throughout plumbing
pages. -IPC 106.3.1