Permit Number: TC-COM-0923-02246
Parcel: 14036349A

Review Status: Approved

Review Details: RESTAMP - COMMERCIAL v.4

Permit Number - TC-COM-0923-02246
Review Name: RESTAMP - COMMERCIAL v.4
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2024 Site Engineering APPROVED
03/22/2024 Site Zoning APPROVED
03/26/2024 Bldg Permits - Post Review REVIEW COMPLETED
03/26/2024 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 9/28/2023 3:28:33 PM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 9/28/2023 2:00:47 PM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 10/5/2023 1:11:53 PM
Electrical Review
By: Ron Ross PE
1 E0.0 GENERAL NOTES: Sheet index missing sheet E4.1 Equipment Schedule.

3 E1.0 SITE PLAN: Missing Keynote 10.

7 E3.0 SINGLE LINE: Could not locate Keynote 2.

9 E4.1 EQUIPMENT SCHEDULE: Keynote 2 is in error for F2 as it needs a 3 pole disconnect per Volts and Wire Callout.

10 E5.0 SITE PHOTOMETRIC PLAN: Tucson City has a maximum lumens per Acre and lamp lighting cutoff requirement for exterior lighting vs the provided IECC exterior lighting comcheck which is accepted for this review. However, the web URL to reference the proper calculations and table are in Chapter 4: https://www.tucsonaz.gov/files/sharedassets/public/v/1/cityservices/planning-development-services/documents/2012_outdoor_lighting_code_.pdf


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved with Comments
Reason:
Date Completed : 3/23/2024 2:21:34 PM
Fourth Plumbing Review: OK Subject to field inspections
Resolved-1). Water piping & water piping fittings on plan page P1.3 are not compatible. & doesn't correlate with water piping materials on plan page P1.2 -IPC 605

Resolved-2). Carwash water connection on plan page P1..2 needs RPZ Backflow preventer. -IPC 608 ** the RPZ needs to be located on branch supplying car wash**

Resolved-3). Storm drain calculation table on P1.1 is using the incorrect rainfall rate -Tucson Plumbing Code Amendments.

Resolved-4). Horizontal portion of 3" roof drain conductors on P1.1 will need 1/4" slope -IPC 1106.2

Resolved-5)., HOT piping still not shown to washer on plan page P1.2 only cold is show. Illustrate the required hot water piping & its source on plan page P1.2 according to -2018 IPC 607.1

Resolved-6). Plan set missing Pages C4.1, 4.2, 4.3 for continuation of water service & sewer as stated throughout plumbing pages. -IPC 106.3.1
03/22/2024 Fire New Construction REVIEW COMPLETED
03/25/2024 Water - PDSD REVIEW COMPLETED