Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0923-02183
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/28/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
09/28/2023 | Commercial Plumbing | REQUIRES RESUBMIT | 1. A cleanout is required at the junction of the building drain and the building sewer (30” in developed length beyond the exterior walls of the building) or within 10 feet of developed length upstream of the junction. A 2-way cleanout is only allowed within this area. Other locations require a cleanout that allows cleaning only in the direction of flow. Reference: Sections 202, 708.1.3, and 708.1.8, IPC 2018. 2. The revised splash pad drawing does not show a vent for the new floor sink. The vent may be located up to 12’ from the trap weir. Reference: Section 909.1, IPC 2018. 3. Provide the first-floor elevation of the splash pad equipment room and compare it to the rim elevation of the next upstream sanitary manhole (2538.78’). Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson. |
||
09/28/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |