Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0923-02168
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/01/2024 | Water Sterilization Report (Deferred Submittal) Express | APPROVED | |||
| 04/01/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/01/2024 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | Exhaust for room 125 (EF-1) is 45% below design. Engineer of record to review and determine corrective action. | ||
| 03/28/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |