Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0826-01223
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/26/2026 | Commercial Building Standard | APPROVED | |||
| 08/26/2026 | Commercial Plumbing Standard | APPROVED | |||
| 08/28/2026 | Site Zoning Standard | APPROVED | |||
| 08/26/2026 | Water - PDSD Standard | APPROVED | |||
| 08/20/2026 | Outdoor Lighting Standard | NOT REQUIRED | |||
| 08/06/2026 | Site Engineering Standard | NOT REQUIRED | |||
| 08/28/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/20/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Conductor is undersized per NEC 240.4(E)(8) 10 AWG Copper. 30 amperes max. Reference sheet E4, Panel H1, Circuit 8,10,12, DU-2 unit. |
||
| 08/26/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Explain how the heating and cooling load calculations for CU-1 and CU-2 are able to justify the heating/cooling capacities of the specified variable refrigerant volume (VRV) split systems. Reference: Section C403.1.1 and C502.2.3, IECC 2024. 2. The new storage room (IT room?) is served by both a ductless split system heat pump (DCU-1/DHP-1) and a VRV split system (CU-1/FC-14). Clarify how this complies with Section C403.3.1, IECC 2024 (i.e., is this a standby or backup system?). Reference: C502.2.3, IECC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 08/26/2026 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 08/06/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |