Permit Review Detail
Review Status: In Review
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0826-01223
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/20/2026 | Outdoor Lighting Standard | NOT REQUIRED | |||
| 08/06/2026 | Site Engineering Standard | NOT REQUIRED | |||
| N/A | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| N/A | Commercial Building Standard | PENDING ASSIGNMENT | |||
| N/A | Commercial Mechanical Standard | PENDING ASSIGNMENT | |||
| N/A | Commercial Plumbing Standard | PENDING ASSIGNMENT | |||
| N/A | Fire New Construction Standard | PENDING ASSIGNMENT | |||
| N/A | Site Zoning Standard | PENDING ASSIGNMENT | |||
| N/A | Water - PDSD Standard | PENDING ASSIGNMENT | |||
| 08/20/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Conductor is undersized per NEC 240.4(E)(8) 10 AWG Copper. 30 amperes max. Reference sheet E4, Panel H1, Circuit 8,10,12, DU-2 unit. |
||
| 08/06/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |