Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2026 Outdoor Lighting Standard NOT REQUIRED
08/06/2026 Site Engineering Standard NOT REQUIRED
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Commercial Building Standard PENDING ASSIGNMENT
N/A Commercial Mechanical Standard PENDING ASSIGNMENT
N/A Commercial Plumbing Standard PENDING ASSIGNMENT
N/A Fire New Construction Standard PENDING ASSIGNMENT
N/A Site Zoning Standard PENDING ASSIGNMENT
N/A Water - PDSD Standard PENDING ASSIGNMENT
08/20/2026 Commercial Electrical Standard REQUIRES RESUBMIT Conductor is undersized per NEC 240.4(E)(8) 10 AWG Copper.
30 amperes max. Reference sheet E4, Panel H1, Circuit 8,10,12, DU-2 unit.
08/06/2026 PDSD Application Completeness Express REVIEW COMPLETED