Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0825-01557
Parcel: 12212029D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0825-01557
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2026 Site Engineering Standard NOT REQUIRED
02/19/2026 Site Zoning Standard NOT REQUIRED
02/24/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/20/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please amend the plans to include structural details demonstrating how the new HVAC equipment is connected to, supported by, and braced from the building structure. The detail shall clearly indicate attachment methods, support members, and any required bracing to ensure structural stability. 2018 IBC Section 107.2.1
Additionally, please provide structural design calculations and an evaluation demonstrating that the existing metal building is capable of resisting the additional loads imposed by the new HVAC equipment. IBC 107.2.7
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
02/12/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0825-01557 (4443 E SPEEDWAY BL TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide updated electrical sheets and equipment lists showing the new electrical HVAC units.
2. Provide updated electrical panel schedule, load calculations and circuiting details. NEC 220.40, NEC arts;300 and 408.4. IBC 107.1.
02/19/2026 Commercial Mechanical Standard REQUIRES RESUBMIT The proposed revision to the HVAC system is too extensive to be covered by a written description. Provide revised drawings that show the extent of the revision to the mechanical, plumbing, electrical, and structural designs.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
02/24/2026 Fire New Construction Standard REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
02/02/2026 PDSD Application Completeness Express REVIEW COMPLETED