Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0825-01553
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/02/2025 | Commercial Building | APPROVED | |||
| 11/18/2025 | Commercial Electrical | APPROVED | |||
| 12/01/2025 | Commercial Plumbing | APPROVED | |||
| 12/01/2025 | Water - PDSD | APPROVED | |||
| 12/12/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/03/2025 | Addressing Validation | REQUIRES RESUBMIT | Complete address missing from updated plans submitted. Please resubit plans and add complete address to include unit number. Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf | ||
| 12/01/2025 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, 504.4 and, 504.6, IMC 2018. 2. Revise the mechanical design as required to avoid using the egress routes as return air ducts (e.g., Facial Room and Break Room). Reference: Section 601.2, IMC 2018. 3. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018. 4. Correct the address for this building permit. Coordinate with Pima County addressing department at 520-724-9512 (the Suite or Unit address number is missing). |
||
| 12/05/2025 | Fire New Construction | REVIEW COMPLETED | |||
| 11/17/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |