Permit Number: TC-COM-0825-01553
Parcel: 12006316B

Address:
4225 S 6TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0825-01553
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2025 Commercial Building APPROVED
11/18/2025 Commercial Electrical APPROVED
12/01/2025 Commercial Plumbing APPROVED
12/01/2025 Water - PDSD APPROVED
12/12/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/03/2025 Addressing Validation REQUIRES RESUBMIT Complete address missing from updated plans submitted. Please resubit plans and add complete address to include unit number. Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
12/01/2025 Commercial Mechanical REQUIRES RESUBMIT 1. Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, 504.4 and, 504.6, IMC 2018.
2. Revise the mechanical design as required to avoid using the egress routes as return air ducts (e.g., Facial Room and Break Room). Reference: Section 601.2, IMC 2018.
3. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
4. Correct the address for this building permit. Coordinate with Pima County addressing department at 520-724-9512 (the Suite or Unit address number is missing).
12/05/2025 Fire New Construction REVIEW COMPLETED
11/17/2025 PDSD Application Completeness Express REVIEW COMPLETED