Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0825-01534
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/28/2025 | Commercial Electrical Standard | APPROVED | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 8/20/2025 10:05:12 AM |
||
| 08/28/2025 | Commercial Plumbing Standard | APPROVED | Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Approved Reason: Date Completed : 8/24/2025 2:24:20 PM |
||
| 09/08/2025 | Water - PDSD Standard | APPROVED | |||
| 08/25/2025 | Outdoor Lighting Standard | NOT REQUIRED | Outdoor Lighting per TC-COM-0725-01290 (3105 N CAMPBELL AV TUCSON, AZ 85719) | ||
| 09/08/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/28/2025 | Commercial Building Standard | REQUIRES RESUBMIT | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Approved Reason: Date Completed : 8/27/2025 9:32:44 PM Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Denied Reason: Date Completed : 8/20/2025 1:08:23 PM 1. Sheet T004/Sprinkler System: A sprinkler system has not been provided. The occupant load exceeds 100 occupants and therefore a sprinkler system will need to be provided. Provide a sprinkler system. (2018 IBS Section 903.2.1.2). 2. Sheet T004/Occupant Load Factors: The occupant load factor for the kitchen is incorrect. PRovide a corrected occupant load calculation for the kitchen. (2018 IBC Table 1004.5) |
||
| 08/28/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Denied Reason: Date Completed : 8/28/2025 12:19:42 PM 1. General - COMcheck Compliance statement references ASHRAE 90.1 (2016). ASHRAE 90.1 (2016) is not an adopted code reference in Tucson, AZ. The Adopted code reference in Tucson, AZ is the 2018 IMC and the 2018 IECC - 2018 IECC Section C103.2Information on construction documents. - 2018 IBC Section [A]107.2.1Information on construction documents. - 2018 IECC Section C403.3.2 HVAC equipment performance requirements. |
||
| 08/29/2025 | Site Engineering Standard | REQUIRES RESUBMIT | Permit: TC-COM-0825-01534 Location: 3105 N CAMPBELL AV Review Date: 8/29/2025 Site Engineering Comments: 1. This site resides within the Wilson Avenue AE Floodplain and will require a flood plain use permit for work within the Flood plain. This can be applied for within the Sub-records of permit TC-COM-0825-01534. Ensure to submit the construction plans as part of the submission for the FPU permit. If you have any questions or concerns, please contact Marco Contreras Marco.contreras@tucsonaz.gov |
||
| 09/05/2025 | Site Zoning Standard | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-0825-01534 - TD-DEV-0425-00116 5530 E BROADWAY BL - C-1 Food Service (1st Review) TRANSMITTAL DATE: ‎September 5, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the C-1 zone (UDC 4.7.20). Food Service is a permitted use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 & 5 and 4.9.13.O 1. The outdoor patio area shown on the plan does not match what is shown on the approved DP TD-DEV-0425-00116. On of the plans will need to be revised so that they match. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 09/03/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 08/15/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |