Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3
Permit Number - TC-COM-0825-01471
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/10/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/10/2025 | Commercial Plumbing Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0825-01471 ADDRESS/PARCEL: (1681 W PRINCE RD Unit:UNIT 19 TUCSON, AZ 85705) Comments: 1. Verify the minimum available water pressure for this address with Flowing Wells Irrigation District. Revise the water calculations as required. 2. Revise the water distribution system design criteria to account for the actual static lift to the highest fixture. Reference: Section 604.1, IPC 2018, as amended by the City of Tucson. 3. Revise the water pressure calculations to include the pressure drop due to the reduced pressure backflow preventer. Reference: Section 604.1, IPC 2018. 4. Revise the design criteria of the water distribution system to provide a flow pressure of 15 PSI or the flow pressure prescribed by the fixture or appliance manufacturer, whichever is greater. Reference: Section 604.3, IPC 2018, as amended by the City of Tucson. |
||