Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-0825-01471
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/28/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/28/2025 | Commercial Plumbing Express | REQUIRES RESUBMIT | The provided pipe sizing calculations are incomplete and the pipe main appears to be undersized for the stated water demand. Section 604.1, IPC 2018 allows water distribution systems to be designed using accepted engineering methods. Provide the source of the method used to determine the water demand and size the water distribution system. [Initial comment: Provide calculations showing how the water supply piping has been sized. Reference: Section 603.1, IPC 2018.] | ||
| 08/26/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |