Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0825-01471
Parcel: 10612016A

Address:
1681 W PRINCE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0825-01471
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/28/2025 Commercial Plumbing Express REQUIRES RESUBMIT The provided pipe sizing calculations are incomplete and the pipe main appears to be undersized for the stated water demand. Section 604.1, IPC 2018 allows water distribution systems to be designed using accepted engineering methods. Provide the source of the method used to determine the water demand and size the water distribution system. [Initial comment: Provide calculations showing how the water supply piping has been sized. Reference: Section 603.1, IPC 2018.]
08/26/2025 PDSD Application Completeness Express REVIEW COMPLETED