Permit Number: TC-COM-0824-01621
Parcel: 12509012A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0824-01621
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2024 Site Zoning APPROVED
09/05/2024 Water - PDSD APPROVED
09/09/2024 Site Engineering NOT REQUIRED
09/09/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
09/06/2024 Commercial Building REQUIRES RESUBMIT Sheet A0.0 For questions in regards to review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179. All applicable comments to be followed by the initials (BM)
1. Sheet A1.0 Identified keynote #20 at exterior wall is not listed in keynotes section. Clarify 2018 IBC 107.2.1 (BM)
2. Sheet A1.0 Identify existing or new roof access to mechanical equipment to comply with 2018 IMC 306.5 (BM)
3. Sheet A2.0 Provide for review, structural detail for new opening in existing CMU / Brick wall. Also provide detail for infill of openings. Incomplete 2018 IBC 107.2.1 (BM)
4. Sheet A2.1 Cycle room is identified with a stage / platform. Will need to provide details for construction. Will need to include all dimensions, height and access stairs to comply with 2018 IBC 410.2, 410.3 & section 1011. (BM)
5. Sheet A3.0 Identify on plans if mechanical units HP1, HP2 & HP3 are existing or new on existing approved support curbs. Provide detail for new support curb and structural information for unit weight on existing roof and details for openings in roof. Not clear on plans. 2018 IBC 107.2.1 (BM)
09/06/2024 Commercial Electrical REQUIRES RESUBMIT Sheet E2.0 Building is identified with two exits. Exit signs need to be placed to identify direction to all exits at both hallway door openings to comply with 2018 IBC 1013.1 (BM)
09/06/2024 Commercial Mechanical REQUIRES RESUBMIT Sheet M2.0 Identify if units are in a location that will require guards or fall protection if less than 10' from edge of roof and parapet is less than 42" in height to comply with 2018 IMC 304.11 (BM)
09/06/2024 Commercial Plumbing REQUIRES RESUBMIT Sheet P2.0 Provide pan and pan drain under water heater for interior wall protection per 2018 IPC 504.7 & 504.7.1 (BM)
08/29/2024 Fire New Construction REVIEW COMPLETED
08/21/2024 PDSD Application Completeness REVIEW COMPLETED