Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0824-01597
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/19/2024 | Commercial Structural | APPROVED | |||
09/18/2024 | Site Zoning | NOT REQUIRED | Charter schools exempt from zoning | ||
09/23/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/30/2024 | Commercial Electrical | REQUIRES RESUBMIT | Permit Review TC-COM-0824-01597 (440 N GRANDE AV Unit:BLDG 3 TUCSON, AZ 85745) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Provide circuiting information for the under-canopy lighting, including conductor, conduit, OCPD and circuit number. 2. Provide disconnect means as required per 225.31- 225.32 for the lighting circuits. 3. Provide complete Grounding details for the metal structure per NEC 690.43. 4. Provide a Grounding Electrode System at the detached structure per NEC 690.47. Outdoor lighting: 5. Show the proposed outdoor lighting fixtures as full cut-off (FCO) style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Provide the manufacturer’s spec sheets for the lighting fixtures. 6. Show lamps with a maximum of 3500K color temperature, OLC 402.1. 7. Full Cut Off fixtures under an overhang or canopy are exempt from the calculation, OLC 4.2.1. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
09/23/2024 | Site Engineering | REQUIRES RESUBMIT | Please address Electrical comments. Site Engineering has no objections to the proposed installations. Chris Arrington chris.arrington@tucsonaz.gov |
||
08/30/2024 | Fire New Construction | REVIEW COMPLETED | |||
08/22/2024 | PDSD Application Completeness | REVIEW COMPLETED |