Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0824-01534
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/21/2024 | Commercial Electrical | APPROVED | |||
08/21/2024 | Site Zoning | APPROVED | |||
08/21/2024 | Water - PDSD | APPROVED | |||
08/26/2024 | Site Engineering | NOT REQUIRED | |||
08/26/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
08/22/2024 | Commercial Building | REQUIRES RESUBMIT | For inquiries on comments email ekulik@willdan.com 1. Sheet A-2 Coordinate with electrical plan regarding the existing SES. 2. Sheet E2.0 See sheet A2.0 regarding electrical SES, it shows that the existing service is being upgraded to an 800amp service. Coordinate the information as to what is the existing SES. |
||
08/22/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Sheet MP2.1 Provide slab repair details where new underground plumbing is being installed. (EK) | ||
08/22/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Provide Address Specific letter regarding this projects Grease Interceptor. This will be part of the plan review documentation. (EK) | ||
08/19/2024 | Fire New Construction | REVIEW COMPLETED | |||
08/08/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |