Permit Number: TC-COM-0824-01534
Parcel: 134130580

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0824-01534
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2024 Commercial Electrical APPROVED
08/21/2024 Site Zoning APPROVED
08/21/2024 Water - PDSD APPROVED
08/26/2024 Site Engineering NOT REQUIRED
08/26/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/22/2024 Commercial Building REQUIRES RESUBMIT For inquiries on comments email ekulik@willdan.com
1. Sheet A-2 Coordinate with electrical plan regarding the existing SES.
2. Sheet E2.0 See sheet A2.0 regarding electrical SES, it shows that the existing service is being upgraded to an 800amp service. Coordinate the information as to what is the existing SES.
08/22/2024 Commercial Mechanical REQUIRES RESUBMIT Sheet MP2.1 Provide slab repair details where new underground plumbing is being installed. (EK)
08/22/2024 Commercial Plumbing REQUIRES RESUBMIT Provide Address Specific letter regarding this projects Grease Interceptor. This will be part of the plan review documentation. (EK)
08/19/2024 Fire New Construction REVIEW COMPLETED
08/08/2024 PDSD Application Completeness Express REVIEW COMPLETED