Permit Number: TC-COM-0824-01532
Parcel: 116163120

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0824-01532
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/03/2025 External Reviewers - Stantec Express REQUIRES RESUBMIT January 31, 2025
1st Review

Intertech Architectural Interiors, Inc.
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: BLEND (SPEEDWAY)
NEW BUILDING (DEFERRED SUBMITTAL)

City of Tucson Permit Number: TC-COM-0824-01532
Stantec Project Number: 185215066
Stantec File Number: TUC-25-020

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 800 6 No No
Separate Permits: Signage.
Deferred Submittals: Plywood web joists.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, high-strength bolts, field welding.

GENERAL COMMENTS

1. The Roof Placement Plan and the Details sheet both include stamps that state “Not For Construction”. Plans must be “Final” and “For Construction” to approve.

2. The submittal includes revisions to the structural plans of the original permit. The City of Tucson requires that any plan changes because of a deferred submittal must be submitted separately as a revision. Please remove the structural revisions from the submittal and submit a separate revision to address these changes.

3. The submittal only includes the calculations for joists RJ2 and RJ1. Please provide the calculations for the remainder joist tags.

ARCHITECTURAL COMMENTS

There are no comments.

STRUCTURAL COMMENTS

General

1. The submittal includes revisions to the structural plans of the original permit. The City of Tucson requires that any plan changes because of a deferred submittal must be submitted separately as a revision. Please remove the structural revisions from the submittal and submit a separate revision to address these changes.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/30/2025 PDSD Application Completeness Express REVIEW COMPLETED