Permit Number: TC-COM-0824-01531
Parcel: 10709007C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0824-01531
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2024 Site Engineering APPROVED
09/05/2024 Site Zoning APPROVED
09/09/2024 Water - PDSD APPROVED
09/09/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
08/22/2024 External Reviewers - Stantec REQUIRES RESUBMIT August 19, 2024
1st Review

Light+Path Architecture LLC.
Attn: Brian G. Hagedon
475 S. Gollob Rd.
Tucson, Arizona 85710

Re: TEEN CHALLENGE - BLDG. 1 STUDENT SERVICES
SHELL, CORE, FITOUT

City of Tucson Permit Number: TC-COM-0824-01531
Stantec Project Number: 185215066
Stantec File Number: TUC-24-110

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 V-B 29,312 579 Yes Yes
R-2
Separate Permits: Automatic fire sprinklers, fire alarm, and kitchen hood suppression system.
Deferred Submittals: Wood I-joists, steel stairs, and elevator shop drawings.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, structural steel, high-strength bolts, field welding, and cold-formed metal deck.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903], fire alarm system [2018 IBC Sec. 907], and kitchen hood suppression system [2018 IBC Sec. 904.12] are to be provided as part of this project and are to be submitted as a separate permit.

3. Please indicate that the elevator shop drawings will be provided as part of deferred submittal and list on the cover sheet as a deferred submittal and include the following notes:

PER IBC Section 107.3.4
<Name of Registrant>, the registered design professional in charge shall be responsible for reviewing and coordinating submittal documents prepared by others, including phased and deferred submittal items, for compatibility with the design of the building.

PER IBC Section 107.3.4.1
Submittal documents for deferred submittal items shall be submitted to the registered design professional in responsible charge, who shall review them and forward them to the Building Official with a notation indicating that the deferred submittal documents have been reviewed and that they have been found to be in general conformance with the design of the building.

Sheet G101

1. Sheet E15 indicated on the sheet index is missing from the plan-set. Please provide.

Sheet GA111

1. Please provide plumbing fixture calculations. [Ref. IBC 2018 Sec. 2902.1]

Sheet GA202

1. The Evaluation Report indicated for the Gold Bond Interior Partition System is based on the 1997 UBC. Please provide an updated ES Report in compliance with the 2018 IBC. [Ref. 2018 IBC Sec. 104.11.1]

2. Please provide the listing and detail for a through-penetration firestop system. [Ref. IBC 2018 Sec. 714.4.1.2]

Sheet A111

1. Please indicate at least 5% of seating and standing spaces as accessible. [Ref. IBC 2018 Sec. 1109.11]

2. Please include the outdoor seating area in the occupant load calculations. [Ref. IBC 2018 Sec. 1004.7]


Sheet A114

1. Please indicate a ceiling schedule mark for room “STG 115”.

2. Please indicate the listing, location, and limits of a horizontal assemble required for the sleeping unit separation. [Ref. IBC 2018 Sec. 711.2.4.3]

Sheet A121

1. The plan-set does not indicate a 1-hour rated wall assembly between the interior exit stairway and the storage room common wall. Please revise. [Ref. IBC 2018 Sec. 1023.2]

STRUCTURAL COMMENTS

General

1. Please provide an updated structural analysis for the Type 1 Hood addressing connection to structure, the concentrated load, and location.

MECHANICAL COMMENTS

General

1. Plans including a commercial kitchen ventilation system shall include a schedule or diagram indicating the design outdoor air balance. The design outdoor air balance shall indicate all exhaust and replacement air for the facility, plus the net exfiltration if applicable. The total replacement air airflow rate shall equal the total exhaust airflow rate plus the net exfiltration. [Ref. IMC 2018 Sec. 508.1.2]

Sheet M101

1. Please indicate duct smoke detector in the return air ducts of air distribution systems moving more than 2,000 cfm. [Ref. IMC 2018 Sec. 606.2.1]

PLUMBING COMMENTS

Sheet 101

1. The callout indicated for FC 1-5 is missing the detail number and sheet. Please revise.

Sheet P105

1. Please provide cleanouts in accordance with Section 708 for the storm drain system. [Ref. IPC 2018 Sec. 1101.8]

Sheet 401

1. Fixture FS is not included in the fixture schedule. Please revise.

ELECTRICAL COMMENTS

Sheet ES101

1. Please indicate the heights of the light poles.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
09/09/2024 Fire New Construction REQUIRES RESUBMIT -Resolve all building comments.