Permit Number: TC-COM-0823-02016
Parcel: 123100280

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0823-02016
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2023 Site Zoning APPROVED
09/18/2023 Water - PDSD APPROVED
08/23/2023 Site Engineering NOT REQUIRED
09/18/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
09/05/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 8/29/2023 4:37:29 PM
1. Proposed scope of work does not appear to impact the existing structure. No review required.




Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 8/29/2023 10:59:15 AM




Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 8/24/2023 10:04:41 PM
Provide VAV Schedule. Show CFM quantities for each VAV - Indicate AHUs feeding VAVs - IBC 2018 – Section [A]107.2.1 Information on construction documents

Provide Commercial Energy Calculations - 2018 INTERNATIONAL ENERGY CONSERVATION CODE section C103.2 & C103.2.1 Construction & Document



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 9/4/2023 9:55:59 AM
Electrical Review of Kids Zone
By: Ron Ross PE
E2.01-1 LIGHTING PLAN - PLAYZONE FLOOR: General Note 7 is not clear



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 9/4/2023 5:01:59 PM
First Plumbing Review:
1). Toilets in Room 13859 on plan page A5.11-1 need partitions -IPC 405.3.4
08/31/2023 Fire New Construction REVIEW COMPLETED
08/21/2023 PDSD Application Completeness REVIEW COMPLETED