Permit Number: TC-COM-0823-01995
Parcel: 117120470

Address:
50 W CONGRESS ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0823-01995
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2023 Site Zoning APPROVED
09/15/2023 Water - PDSD APPROVED
08/23/2023 Site Engineering NOT REQUIRED
09/15/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/18/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/18/2023 4:09:27 PM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/18/2023 4:07:47 PM
1) General: Please provide proof of project valuation.

2) General: Include the specification sheets for the oven to determine if a hood is needed. (2018 IMC section 507.3)

3) Sheet A0.9 (Cover Sheet): The occupancy load for commercial kitchens is calculated at 1 person per 200 sf. (2017 NEC Table 1004.5)

4) Sheet A2.8 (First Floor Plan): Show the entire floor and the uses of the spaces to determine if fire separation is needed per Table 508.4. Detail if dining areas are new or existing. (2018 IBC section 107)

5) Sheets A2.8, A8.9, P1.0, P2.0, E2.1, and E4.1: Plumbing fixtures and equipment (espresso machines, ice machines, and hand sink) shown on the floor plans do not match what is shown on the plumbing and electrical pages. If additional kitchen
equipment (shown on the plumbing plans) is installed, the electrical panel may not be large enough. Please coordinate the plans and revise all applicable sheets. (2018 IBC section 107)

6) Sheet E4.1 (Electrical Panel Schedules): The panel schedule for panel "G" circuits 37, 39, and 41 show they are feeding panel "B1", but the new subpanel is named "G1". (2017 NEC sections 110.22 and 408.4)


Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/18/2023 4:08:53 PM
See the building review comments.


Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/18/2023 4:08:33 PM
See the building review comments.



Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/18/2023 4:09:10 PM
See the building review comments.
08/16/2023 Fire New Construction REVIEW COMPLETED
08/16/2023 PDSD Application Completeness REVIEW COMPLETED