Permit Number: TC-COM-0823-01886
Parcel: 123100280

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0823-01886
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2023 Site Zoning APPROVED
08/08/2023 Site Engineering NOT REQUIRED
08/17/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/17/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 8/17/2023 11:24:56 AM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall
not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 8/9/2023 11:14:14 AM
1. Sheet AD-111: The required smoke barrier is interrupted at the clean supply room. Clearly indicate the continuance of the smoke barrier. Additionally, please show that all smoke barriers meet the continuity requirements of section 709.4.1.

2. Sheet AC-012: Many of the partition types are labeled as smoke partitions. However, smoke barriers are required. Provide the proper partition type for separations requiring smoke barriers in accordance with Section 407.5.




Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 8/6/2023 1:47:52 PM
Approved/Subject to field approval



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 8/16/2023 6:23:14 PM
Electrical Review of BUMCT
By: Ron Ross PE
ED-213 AREA C - BASEMENT FLOOR DEMO PLAN - POWER: Comment, Missing this sheet.

ED-214 AREA D - BASEMENT FLOOR DEMO PLAN - POWER: Sheet is missing keyplan.
E-212 AREA B - OR PLAN - POWER: Isn’t keynote 2 a duplicate of keynote 4 on Sheet
E-211? Same issue with Keynotes 1
and 3. Suggest to make a standard keynote legend and state ‘Not all keynotes used’.

E-801 SCHEDULES - ELECTRICAL: Need to provide interior lighting Comcheck report (Cover page(s) is acceptable) or provide a statement that fewer a Comcheck is not required as less than 10% of the lights are being replaced and the ones that are being replaced are lower wattage than existing. “Or that replaced lights are in critical areas outside the scope of Comcheck.”



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 8/16/2023 10:33:21 PM
First Plumbing Review:
1). Make up water connection on plan page M-702 needs backflow preventer - IPC 608.3

2). Plumbing plans need to include sanitary, venting , water piping configurations for the new and relocated fixtures shown on plan pages P-211 & P212 -IPC 106.3.1 including new restroom

3). Plumbing plans need to show piping configuration detail for the CS-1 sink as labeled on plan page P001 -IPC 106.3.1, 608.3, 609.1

4). Add scrub sink info to plan page P001 -IPC 303

5). plumbing plans do not illustrate the backflow device as stated on plan page M-701 -IPC 608.3
08/13/2023 Fire New Construction REVIEW COMPLETED
08/04/2023 PDSD Application Completeness REVIEW COMPLETED