Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0726-01139
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/17/2026 | Site Engineering Standard | APPROVED | |||
| 08/13/2026 | Site Zoning Standard | APPROVED | |||
| 08/17/2026 | Water - PDSD Standard | APPROVED | |||
| 08/07/2026 | Design Review Standard | NOT REQUIRED | No approved SMD Design Package on file. | ||
| 08/10/2026 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| 08/17/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/14/2026 | Commercial Building Standard | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov 1. Please clarify the specific use proposed under the Group E occupancy classification. For example, is the space intended for educational purposes through the 12th grade, or is it intended to operate as a child day care facility providing educational, supervision, or personal care services to children older than 2½ years of age for fewer than 24 hours per day? IBC 107.2.1 & IBC 305.2 2. Please provide a reflected ceiling plan showing the ceiling height, light fixtures, and supply and return registers. IBC 107.2.1 Please contact me if you have any questions about the above comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 08/10/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0726-01139 (2900 E BROADWAY BL Unit:UNIT 174 TUCSON, AZ 85716) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Existing Building Code (IEBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. Change of occupancy from B to E.. 2. Provide as-built electrical plans as part of this CofO submission. Show existing electrical meets the requirements of the International Existing Building Code, chapter 10, IEBC 1007. |
||
| 08/17/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. (Note: verify that the existing air conditioning system is capable of accommodating the increased cooling load and ventilation requirements for the proposed occupancy.) Reference: Section 403.3.1.1, IMC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 08/17/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | 1. Correct the plumbing fixture calculation shown on sheet a010. A total population of 54 persons will require two restrooms, two drinking fountains, and a service sink. Reference: Sections 2902.1 and 2902.2, IBC 2024. 2. Provide a minimum of two drinking fountains; one accessible for standing persons and one accessible for persons confined to a wheelchair. Reference: Section 410.3.1, IPC 2024 (see also exception 1,Section 410.3 and Section 410.4, IPC 2024, as amended by the City of Tucson). If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov |
||
| 08/17/2026 | Fire New Construction Standard | REQUIRES RESUBMIT | -Resolve all building comments. -Include all fire alarm information in the code analysis. IFC 907.2.3, FA is required in Group E occupancies. -Fire sprinklers are not required in this occupancy. Keep in mind, there is an IFC amendment to the fire sprinkler requirement for Group E, 903.2.3. john.vincent@tucsonaz.gov 5203495581 |
||
| 07/27/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |