Permit Number: TC-COM-0726-01122
Parcel: 13321155A

Address:
201 N JESSICA AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0726-01122
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2026 Commercial Plumbing Standard APPROVED
09/24/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/24/2026 Commercial Mechanical Standard REQUIRES RESUBMIT The area in question is enclosed on three sides by wall that extend to the ceiling and provides a path of egress travel. That is basically the definition of a corridor. [Initial comment: Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2024.]
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
09/16/2026 PDSD Application Completeness Express REVIEW COMPLETED