Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0726-01122
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/24/2026 | Commercial Plumbing Standard | APPROVED | |||
| 09/24/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/24/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | The area in question is enclosed on three sides by wall that extend to the ceiling and provides a path of egress travel. That is basically the definition of a corridor. [Initial comment: Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2024.] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 09/16/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |