Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0725-01427
Parcel: 14037068J

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0725-01427
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2025 Commercial Building Standard APPROVED
08/25/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/14/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0725-01427 (5570 E TRAVEL PLAZA WY TUCSON, AZ 85756)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Electrical Review:
1. Reference sheet E-3.0, Short Circuit Information note: Provide Fault Current Analysis and show new equipment AIC rating sufficient to withstand the calculated Fault Current. Provide Available Fault Current calculations from TEP transformers to all new equipment, 2017 NEC 110.24.
2. Show new Panel’s and other new equipment with AIC ratings greater than or equal to the Available Fault Currents calculated, 2017 NEC 110.10.

Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf
1. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
2. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
3. Fixtures installed under canopies and overhangs. Outdoor lighting fixtures shall not be counted in determining the total light output when they are full cutoff light fixtures installed under canopies, building overhangs, or roof eaves, OLC 401.2.1(3).
4. Provide manufacture’s specification sheets for outdoor lighting fixtures.

5. Specify any exceptions used.

6. Provide Curfew lighting controls If applicable Per section 403 and Table 601.3.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
08/12/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-0725-01427
Location: 5570 E TRAVEL PLAZA WY
Review Date: 8/12/2025
Site Engineering Comments:
1. The location of the proposed EV parking and charging stations do not appear to match what is called out in the development package TD-DEV-0523-00245. If these plans are to be reviewed and approved, the DP will need to be revised to match with what is being proposed in commercial permit TC-COM-0725-01427.

If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
08/25/2025 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0725-01427 – TD-DEV-0523-00245
5570 E. Travel Plaza Wy Tucson, AZ 85756
New EV Charging Station (1st Review)

TRANSMITTAL DATE: 8/25/2025

This site is located in the C-2 zone (UDC 4.7.21).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: The location of the proposed EV charging stations does not match what was previously approved in the development package (TD-DEV-0523-00245). The development package and the building permit need to match. Please either revise the development package to update the new EV location or place them in their previously approved location.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
08/19/2025 Fire New Construction Standard REVIEW COMPLETED
08/04/2025 PDSD Application Completeness Express REVIEW COMPLETED