Permit Number: TC-COM-0725-01397
Parcel: 11307017B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0725-01397
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2025 Site Zoning Standard APPROVED
08/01/2025 Site Engineering Standard NOT REQUIRED
08/13/2025 Water - PDSD Standard NOT REQUIRED
08/13/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/04/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please amend plans to provide a detailed description of the work involved in this permit’s scope to include all unit numbers. IBC 105.3 Additionally, were any new interior walls constructed? Please state the rating of the separation walls between the two units. Were these altered during the remodel. IBC 107.2.1
2. Please expand on the description for the pool and deck pool refurbishing to add more detail, show the main drain(s) and show the drain cover types used to prevent hair and body entrapment. IBC 107.2.1
3. Please apply for a separate permit for each structure and the pool using a Master Permit. We typically do the Master Permit at the beginning (prior to any reviews). 107.2.1
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/submitting-for-multiple-permits-on-one-plan-set.pdf
Submitting for Multiple Permits on one Plan Set - Official website of the City of Tucson
Visit Us | TDC-Online.tucsonaz.gov | Public Works Building 1st floor, 201 N. Stone Avenue | Page 1 of 5. Submitting for Multiple Permits on one Plan Set . 1. Go to TDC Online, for best results use a Google Chrome browser. 2. Register or Log In, using your email address.

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
08/04/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0725-01397 (1651 E GLENN ST TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).


1. Provide protection of all interior 15A & 20A circuits serving outlet locations (except garage, and bathrooms) including receptacles, lights and smoke detectors, with combination type arc-fault circuit interrupters, IRC E3902.21 [NEC 210.12(A)].

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
08/13/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. The 2018 International Mechanical Code and the 2018 International Fuel Gas Code with Local Amendments are the relevant codes for this project, not the International Residential Code.
2. Clarify the proposed scope of work on sheet 6. Are the combustion & relief vents being changed? Is the dryer exhaust being brought up to current code (the vent should be 4” in diameter, not rectangular)?
3. Replacement of AC units will require heating/cooling load calculations to justify the capacities of the units being installed (Sections R403.7, IECC 2018). The units themselves will also have to comply with Sections R403.1 and R503.1.2, IECC 2018 for controls. The replacement units shall have an efficiency rating that is greater than or equal to the minimum required by the Department of Energy requirements that went into effect on January 1, 2023 for the Southwest part of the country.
4. Apply for a separate permit for each structure.
08/13/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Apply for a separate permit for each structure.
2. The description of work for this activity is to replace a water heater. If it is a like-for-like replacement, submit documents that describe the proposed water heater (e.g., Manufacturer specifications). Reference: Section 107.2.1, IBC 2018.
3. Specify that all proposed plumbing fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018.
08/07/2025 Fire New Construction Standard REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
08/04/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0725-01397 (1651 E GLENN ST TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Outdoor Lighting Review:

1. REF Sheet 8, Scope of Work note #6: This note indicates that the outdoor lights over the doors of each unit will be replaced. This requires that these light fixtures meet the outdoor lighting code.
2. Fixtures installed under canopies and overhangs. Outdoor lighting fixtures shall not be counted in determining the total light output when they are full cutoff light fixtures installed under canopies, building overhangs, or roof eaves, OLC 401.2.1(3).
3. Either show all replaced outdoor lighting fixtures as full cutoff and under an overhang, or provide the calculations and plans as required in comments 4-10.
4. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
5. Show lamps with a maximum of 3500K color temperature, OLC 402.1. There are two fixture schedules and one shows color temperatures of 4000k, see sheet E1.1.
6. Show compliance with total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4.
7. Submit catalogue or specification sheets of all proposed new outdoor lighting fixtures illustrating the type of fixture, color temperature, lumens rating and whether full cut-off or unshielded.

8. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

9. Specify any exceptions used.

10. Provide Curfew lighting controls If applicable Per section 403.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
07/22/2025 PDSD Application Completeness Express REVIEW COMPLETED