Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.3
Permit Number - TC-COM-0725-01373
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/16/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/16/2026 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | Comment not resolved; the submitted document is not an air balance report, it is a heating/cooling load calculation. [Initial comment: The air balance report shows that the existing HVAC system is unable to supply the required ventilation for the restaurant and only one of the two existing AC units is operational. Submit the report to the responsible engineer who will determine the needed corrective actions. Once the corrective actions have been accomplished, retest the HVAC system and submit the results. ] | ||
| 01/13/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |