Permit Number: TC-COM-0725-01369
Parcel: 141114050

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0725-01369
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2025 Commercial Electrical Express APPROVED
07/16/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/16/2025 Commercial Mechanical Express REQUIRES RESUBMIT The portion of the building being modified in this activity does not appear to have been conditioned. Section C503.2, IECC 2018 requires the space to be brought into full compliance with the current energy code. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, IECC 2018.
07/15/2025 PDSD Application Completeness Express REVIEW COMPLETED