Permit Number: TC-COM-0725-01361
Parcel: 14039052F

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0725-01361
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2025 Commercial Electrical APPROVED
07/21/2025 Outdoor Lighting APPROVED
08/08/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/25/2025 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Structural:
Please provide stamped and sealed structural calculations prepared by an Arizona licensed registrant used in the design of the following items.
A. Sheet A1.1
i. Trash Enclosure walls and foundation
ii. Chain Link Sliding Gate and associated fencing
iii. Mechanical Enclosure walls and foundation
B. Sheet S2.0
i. Light Pole Base- Cassion foundation
C. Sheet A5.0
i. Keynote 4. Entry Canopy attachment connections and provide an evaluation of PEMB walls supporting this additional load.
ii. Keynote 5. Louvered Aluminum Sunshades attachment connections and provide an evaluation of PEMB walls supporting this additional load.
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
07/29/2025 Commercial Mechanical REQUIRES RESUBMIT 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018.
2. Secure the refrigerant circuit access ports of the ground-mounted condensing units to prevent unauthorized access. Reference: Section 1101.10, IMC 2018.
07/29/2025 Commercial Plumbing REQUIRES RESUBMIT 1. A private sewer collection system that includes manholes will require a review of the system design by the Pima County Department of Environmental Quality as well as a building permit from the City of Tucson. In addition, the Pima County Department of Environmental Quality requires the Engineer of Record to conduct specific inspections during construction. Submit the plans that have been approved by the Pima County Department of Environmental Quality for approval. Reference Title 18, R18-9-E302, 4.02 General Permit, Arizona Administrative Code.
2. The specified freeze-proof yard hydrant uses a below-grade stop-and-waste valve. This is prohibited unless an approved upstream backflow prevention device is used to protect the upstream potable water source and the downstream outlets are identified with signs that read, “Caution, Non-potable water, Do Not Drink.”. Reference: Sections 608.8 and 608.9.1, IPC 2018.
08/08/2025 Site Engineering REQUIRES RESUBMIT Permit: TC-COM-0725-01361
Location: 5300 E LOS REALES RD
Review Date: 8/8/2025
Site Engineering Comments:
1. Site Engineering will be unable to review and approve permit TC-COM-0725-01361 until the associated development package TD-DEV-0725-00184 is approved by all reviewers.

If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
07/30/2025 Site Zoning REQUIRES RESUBMIT FROM: Ramiro Olivarez
PDSD Zoning Review Section

PROJECT: TC-COM-0725-01361 - TD-DEV-0725-00184
5300 E LOS REALES RD Unit:BLDG 4 – PAD-14
New Commercial Build (1st Review)

TRANSMITTAL DATE: July 30, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in PAD-14.
1. Comment: Zoning has reviewed the construction of the new commercial building plans for compliance with Development Package (DP) TD-DEV-0725-00184 and all though the plans appear to match until the DP is approved by all review agencies Zoning cannot approve this permit.
2. Comment: Per Section C-5.c. of the PAD-14 Document, “Civic Use Group – Civic Assembly” and “Civic Use Group – Instructional School” are both permitted uses in PAD-14. The PAD-14 Document specifically describes the use for this building as “Administrative Office and Learning Center”.

Clarify, Is this building use for Civic Use Group – Instructional School?

If you have any questions about this transmittal, please contact Ramiro Olivarez at Ramiro.Olivarez@tucsonaz.gov
07/29/2025 Water - PDSD REQUIRES RESUBMIT Clarify the water service to the new building. The Utility plan, C400, identifies the water main serving the domestic and fire services to the building as 12” (Tucson Water keynote 1), 8” (Tucson Water keynote 2), and 6” (note on plan). The water service pipe is 2” (Type K soft copper) on C400 but 2.5” on the plumbing drawings. The reduced pressure backflow preventer is 1.5” on C400 but 2.5” on the plumbing drawing. The civil and plumbing drawings do agree that a 1.5” water meter will be installed. Reference: Section 107.2.1, IBC 2018.
07/28/2025 Fire New Construction REVIEW COMPLETED
07/16/2025 PDSD Application Completeness Express REVIEW COMPLETED