Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2025 Commercial Building APPROVED
10/06/2025 Commercial Mechanical APPROVED
10/06/2025 Water - PDSD APPROVED
10/17/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/06/2025 Commercial Plumbing REQUIRES RESUBMIT Section 608.8, IPC 2018 stipulates that the potable water supply to freeze-proof yard hydrants be protected in accordance with Section 608.14.2, IPC 2018 or Section 608.14.5, IPC 2018, i.e., either a reduced pressure principle backflow prevention assembly or a pressure vacuum breaker assembly, not a dual check valve. [Initial comment: The specified freeze-proof yard hydrant uses a below-grade stop-and-waste valve. This is prohibited unless an approved upstream backflow prevention device is used to protect the upstream potable water source and the downstream outlets are identified with signs that read, “Caution, Non-potable water, Do Not Drink.”. Reference: Sections 608.8 and 608.9.1, IPC 2018.]
10/06/2025 Site Engineering REQUIRES RESUBMIT Permit: TC-COM-0725-01361
Location: 5300 E LOS REALES RD Unit:BLDG 4
Review Date: 10/6/2025
Site Engineering Comments:
1. Site Engineering will be unable to review and approve permit TC-COM-0725-01361 until the associated development package TD-DEV-0725-00184 is reviewed and approved by all reviewers.
If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
10/17/2025 Site Zoning REQUIRES RESUBMIT FROM: Ramiro Olivarez
PDSD Zoning Review Section

PROJECT: TC-COM-0725-01361 - TD-DEV-0725-00184
5300 E LOS REALES RD Unit:BLDG 4 – PAD-14
New Commercial Build (2nd Review)

TRANSMITTAL DATE: October 17, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in PAD-14.

1. Comment: Zoning has reviewed the construction of the new commercial building plans for compliance with Development Package (DP) TD-DEV-0725-00184 and all though the plans appear to match, until the DP is approved by all review agencies Zoning cannot approve this permit.

If you have any questions about this transmittal, please contact Ramiro Olivarez at Ramiro.Olivarez@tucsonaz.gov
10/01/2025 PDSD Application Completeness Express REVIEW COMPLETED