Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0725-01347
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/12/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/12/2025 | Commercial Building Standard | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. 1. Please amend plans to indicate on the cover page that the signage is to be provided as part of this project and is to be submitted as a separate permit (not a deferred submittal). IBC 107.2.1 2. The plans indicate that pre-engineered wood trusses, pre-engineered canopies, the pre-engineered aluminum awnings and trellis will be provided as part of deferred submittal. Either provide the documents now or list on this sheet as a deferred submittal and include the following notes: PER IBC Section 107.3.4 <Name of Registrant>, the registered design professional in charge shall be responsible for reviewing and coordinating submittal documents prepared by others, including phased and deferred submittal items, for compatibility with the design of the building. PER IBC Section 107.3.4.1 Submittal documents for deferred submittal items shall be submitted to the registered design professional in responsible charge, who shall review them and forward them to the Building Official with a notation indicating that the deferred submittal documents have been reviewed and that they have been found to be in general conformance with the design of the building. 3. Please amend plans to note the required special inspection on the cover sheet. For example. Concrete Construction, Masonry Construction, Soils, EIFS and Water-resistive barrier coating. IBC 107.2.1 4. Please provide the special inspection certificate with Part A and Part B, completed with next submittal. IBC 107.2.1 https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf 5. Structural calculations: Please provide a foundation key plan and foundation calculations as a part of the structural calculations or otherwise indicate the method of designing the building foundation. IBC 107.2.7 6. Please update the statement of special inspections to include Steel Construction, if applicable for the trellises, canopies and similar structures. IBC 1704 Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 08/04/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0725-01347 (5 S HOUGHTON RD TUCSON, AZ 85748) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Provide Fault Current Analysis from transformer ‘TL’ and show AIC rating sufficient to withstand the calculated Fault Current at panels ‘L1’ and L2’. NEC 110.10 & 110.24. 2. Show panel ‘MCC-1’ with AIC ratings greater than or equal to the Available Fault Currents calculated, 2017 NEC 110.10. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 08/12/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Condensate drains may not terminate in an area that is not capable of absorbing the condensate flow without surface drainage (e.g. directly over the roof). Condensate drains shall be terminated at an approved disposal location. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson. 2. Provide information on the sequence of operation for the restroom exhaust fans (i.e., CEF-1, CEF-2, and CEF-3) to show that all the air supplied to the restrooms will be exhausted during hours of operation. The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018. |
||
| 08/12/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | 1. The Water Pressure Data in the Water Calculations identifies 34.5 fixture units for the building but the Fixture Units calculation shows 42.5 Fixture units. Why the difference? Reference: Section 107.2.1, IBC 2018. 2. Revise the First Floor Plan – Office and Water Isometric drawings to show the hot water connected to the left side of the lavatories. Reference: Section 607.4, IPC 2018. |
||
| 07/22/2025 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Outdoor Lighting Review TC-COM-0725-01347 (5 S HOUGHTON RD TUCSON, AZ 85748) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). Outdoor Lighting Review: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf 1. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your table and use the same number on your site plan. Label the specification sheets with the same lighting fixture label as in the fixture schedule. 2. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1. 3. Show compliance with total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2. 4. Show compliance with shielding requirements and light trespass per 401.3. 5. Submit catalogue or specification sheets of all proposed new outdoor lighting fixtures illustrating the type of fixture, color temperature, lumens rating and whether full cut-off or unshielded. 6. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. 7. Specify any exceptions used. 8. Provide Curfew lighting controls If applicable Per section 403. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 08/08/2025 | Site Engineering Standard | REQUIRES RESUBMIT | Permit: TC-COM-0725-01347 Location: 5 S HOUGHTON RD Review Date: 8/8/2025 Site Engineering Comments: 1. Site Engineering will be unable to review and approve permit TC-COM-0725-01347 until the associated development package TD-DEV-0525-00144 is approved by all reviewers. If you have any questions or concerns, please contact Marco Contreras Marco.contreras@tucsonaz.gov |
||
| 08/06/2025 | Site Zoning Standard | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-0725-01347 - TD-DEV-0525-00144 5 S HOUGHTON RD. - C-2 Site Fencing (1st Review) TRANSMITTAL DATE: February 12, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the C-2 zone (UDC 4.7.21). Automotive - Minor Service and Repair, Automotive Washing - Full Service is an approved use in the zone (UDC Table 4.8-4), subject to Use Specific Standard 4.9.13.E. 1. Zoning has reviwed the bulding plans for complance with development package (DP) TD-DEV-0525-00144 and although the plans appear to be in compliance until the DP is approved by all review agencies Zoning cannot approve the buildng plans. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 08/11/2025 | Water - PDSD Standard | REQUIRES RESUBMIT | 1. Installation of the water meter is to be 3” from the property line, in the right of way (see Tucson Water Standard Detail SD-309). 2. Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter in locations accessible to Tucson Water for buildings that have chemicals, cleaning agents, or other contaminants that may come in direct contact with water. See Tucson Water Standard Detail 1802. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf |
||
| 08/02/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 07/17/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |