Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0725-01347
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/09/2025 | Commercial Electrical Standard | APPROVED | |||
| 09/25/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/25/2025 | Commercial Building Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0725-01347 ADDRESS/PARCEL: (5 S HOUGHTON RD TUCSON, AZ 85748) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. COMMENTS: 1. Sheet A3.0 RCP Keynotes a. Item 10 (F16 in the electrical plan). b. These LED Accent tape light that are installed at the top of the building parapets and edge of roofs are part of the building structure (not the signs). Therefore, they are to be incorporated as part of the structure building permit. i. Provide a detail in the shape of an “L” that will cover the top and front of the LED light effectively acting as a full cutoff light source where light do not go above horizontal. ii. Sheet E6.0 Light Fixture Schedule 1. Type F16 - Include the lumens as part of the Outdoor Lighting Code calculation. Since it would have a cap over it as suggested above, it can be categorized as full cut off (where you now show as zero lumens). 2. Thank You for submitting the Outdoor Lighting Code special inspection certificate form. a. However, your comment response document mentions you submitted the special inspection certificate form for the Field Special Inspection, no such document was submitted. i. Please submit this form with part A and B completed. 3. Please resubmit. Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976 |
||
| 09/09/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Controlling the restroom exhaust fans with occupancy sensors results in 100% of the supply air delivered to the restroom entering the rest of the building when the restroom is unoccupied. Revise the sequence of operation so that all of the supply air delivered to the restroom is exhausted during the hours of operation. [Initial comment: Provide information on the sequence of operation for the restroom exhaust fans (i.e., CEF-1, CEF-2, and CEF-3) to show that all the air supplied to the restrooms will be exhausted during hours of operation. The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018. | ||
| 09/09/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Correction made to lavatory in room105 but not in room 106. [Initial comment: Revise the First Floor Plan – Office and Water Isometric drawings to show the hot water connected to the left side of the lavatories. Reference: Section 607.4, IPC 2018.] | ||
| 09/16/2025 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Outdoor Lighting Review TC-COM-0725-01347 (5 S HOUGHTON RD TUCSON, AZ 85748) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). Outdoor Lighting Review: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf 1. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 401.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1. 1a). Reference sheet E1.1. The Schedule provided on this sheet shows the quantity of light fixtures and the lumens per lamp but is missing the total lumens per fixture type and the total lumens per all the fixtures. 1b). The provided Schedule is missing lighting fixture ‘F16’ from the list and is required to be added as an unshielded light. 2. Show compliance with total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2. 2a). Due to lighting fixture F16, this site requires compliance with Option 3 from Table 401.1. Provide complete calculations showing compliance with the total lumens (shielded and unshielded) and max unshielded lumens. 2b). Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. F16. 3. Submit catalogue or specification sheets of all proposed new outdoor lighting fixtures illustrating the type of fixture, color temperature, lumens rating and whether full cut-off or unshielded. Include the specification sheets for fixture F16. 4. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. 5. Specify any exceptions used. 6. Provide Curfew lighting controls as applicable Per section 403. Lighting fixture F16 requires curfew settings. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 09/19/2025 | Site Engineering Standard | REQUIRES RESUBMIT | Permit: TC-COM-0725-01347 Location: 5 S HOUGHTON RD Review Date: 9/19/2025 Site Engineering Comments: 1. Site Engineering will be unable to review and approve permit TC-COM-0325-00503 until the associated development package TD-DEV-0525-00144 is approved by all reviewers. If you have any questions or concerns, please contact Marco Contreras Marco.contreras@tucsonaz.gov |
||
| 09/22/2025 | Site Zoning Standard | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-0725-01347 - TD-DEV-0525-00144 5 S HOUGHTON RD. - C-2 Site Fencing (2nd Review) TRANSMITTAL DATE: September 22, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the C-2 zone (UDC 4.7.21). Automotive - Minor Service and Repair, Automotive Washing - Full Service is an approved use in the zone (UDC Table 4.8-4), subject to Use Specific Standard 4.9.13.E. 1. Zoning has reviewed the building plans for compliance with development package (DP) TD-DEV-0525-00144 and although the plans appear to be in compliance until the DP is approved by all review agencies Zoning cannot approve the building plans. If you have any questions about this transmittal, please contact Ramiro Olivarez at Ramiro.Olivarez@tucsonaz.gov. |
||
| 09/09/2025 | Water - PDSD Standard | REQUIRES RESUBMIT | Show the location and size of the “master backflow preventer” (BFP-1?) noted in the water calculations. The civil utility plans in the development package do not show a backflow preventer for either the water service to the building or for the site irrigation system, both of which are required directly after a water meter. [Initial comment: Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter in locations accessible to Tucson Water for buildings that have chemicals, cleaning agents, or other contaminants that may come in direct contact with water. See Tucson Water Standard Detail 1802. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf] | ||
| 09/03/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |