Permit Number: TC-COM-0725-01347
Parcel: 13338005F

Address:
5 S HOUGHTON RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-0725-01347
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2025 Commercial Building Standard APPROVED
10/14/2025 Commercial Plumbing Standard APPROVED
10/14/2025 Outdoor Lighting Standard APPROVED
10/14/2025 Water - PDSD Standard APPROVED
10/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/14/2025 Commercial Electrical Standard REQUIRES RESUBMIT The Sheet index shows 16 electrical pages. But I only find 7 electrical sheets. Previous plan submittals had all 16 pages. I will be requiring resubmittal to ensure all pages are included in the final approved plan set.
10/14/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Comment not resolved: Note 10 of Electrical/Starter/Disconnect Schedule still shows the exhaust fans controlled by an occupancy sensor. No updated sequence of operation provided (and no sheet M0.1). [Second comment: Controlling the restroom exhaust fans with occupancy sensors results in 100% of the supply air delivered to the restroom entering the rest of the building when the restroom is unoccupied. Revise the sequence of operation so that all of the supply air delivered to the restroom is exhausted during the hours of operation.] [Initial comment: Provide information on the sequence of operation for the restroom exhaust fans (i.e., CEF-1, CEF-2, and CEF-3) to show that all the air supplied to the restrooms will be exhausted during hours of operation. The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018.
10/27/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-0725-01347 - TD-DEV-0525-00144
Location: 5 S HOUGHTON RD
Review Date: 10/27/2025
Site Engineering Comments:
1. The development package, TD-DEV-0525-00144, must be approved by all reviewers prior to the approval of this commercial building permit. UDC Article 3.3.3.7.a
If you have any questions or concerns, please contact
Dylan Molina
Dylan.Molina@tucsonaz.gov
10/28/2025 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Krista Hansen
Planning & Development Services Department – Zoning Review Section

PROJECT: TC-COM-0725-01347 - TD-DEV-0525-00144
5 S HOUGHTON RD
New Commercial Building – Mister Car Wash (3rd Review)

TRANSMITTAL DATE: 10/28/2025


COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Automotive - Minor Service and Repair, Automotive Washing - Full Service is an approved use in the zone (UDC Table 4.8-4), subject to Use Specific Standard 4.9.13.E.


01. COMMENT: Zoning has reviewed the building plans for compliance with development package (DP) TD-DEV-0525-00144 and although the plans appear to be in compliance until the DP is approved by all review agencies Zoning cannot approve the building plans.

For questions regarding Zoning comments, please contact me at: Krista.Hansen@tucsonaz.gov
10/07/2025 PDSD Application Completeness Express REVIEW COMPLETED