Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0724-01458
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/15/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/15/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Revise the natural gas pipe replacement drawing to clearly show: a. The location of the gas meters b. The gas delivery pressure (e.g., 7” WG, 2 PSIG, or 5 PSIG) c. The gas load for each piece of equipment in BTUH d. The developed pipe length from the meter to each piece of equipment e. The size and material of each pipe segment. 2. State the material being used for the water distribution piping. |
||
07/30/2024 | PDSD Application Completeness | REVIEW COMPLETED | Note that this permit is only for unit 2 a separate permit is required for unit 4. |