Permit Number: TC-COM-0724-01450
Parcel: 14002002C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0724-01450
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2024 Commercial Building APPROVED
08/14/2024 Commercial Mechanical APPROVED
08/14/2024 Commercial Plumbing APPROVED
08/14/2024 Water - PDSD APPROVED
08/15/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
08/14/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1. Ref; Plan Sheet E5.0.

1a. Please indicate what electrical equipment feeds the new 400 amp panel ‘B’. Show the OCPD rating and load calculations in order to verify capability.

1b. How does the ETR 400 amp panel ‘A’ correlate with the line diagram and this project?

1c. The note at the Line Diagram states,” ONE LINE DIAGRAM PROVIDED AS PART OF FLEET SERVICE UPGRADE”. For clarity, please show the complete line diagram and clarify what is meant by the note, “PART OF FLEET SERVICE UPGRADE”. Is the service being upgraded under a separate permit?

2. Ref; Plan Sheet E2.0.

2a. Provide a note requiring the receptacles in the Garage areas are to be GFI protected, NEC 511.12.

3. Ref; Plan Sheet E1.0. Provide complete compliance with the 2012 City of Tucson Outdoor Lighting Code for the exterior lighting on the lighting plan or indicate any exception section(s) if applicable.

Ref; 2018 IBC section107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code.
08/15/2024 Site Engineering REQUIRES RESUBMIT see zoning comment
08/13/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0724-01450 - TD-DEV-0524-00157
3950 E IRVINGTON RD. – PAD-34
Generating System (1st Review)

TRANSMITTAL DATE:‎August 13, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in PAD-34 (UDC 4.7.24). Generating System is a permitted use in the PAD.

1. COMMENT: Zoning has reviewed the building plan for compliance with TD-DEV-0524-00157 and the following comment needs to be addressed.

2. The proposed containment area shown on sheet x1.2 could not be found on DP TD-DEV-0524-00157 or any other approved DP for this site. Either ensure that the containment area is shown on TD-DEV-0524-00157 or provide a copy of an approved DP where this containment area is shown.

3. Zoning cannot approve the building plans until the DP is approved by all review agencies.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/09/2024 Fire New Construction REVIEW COMPLETED
07/30/2024 PDSD Application Completeness REVIEW COMPLETED