Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0724-01450
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/21/2024 | Site Engineering | APPROVED | |||
10/18/2024 | Site Zoning | APPROVED | |||
10/21/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/17/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. Previous electrical plan review comment #3 (Outdoor Lighting) not addressed clearly. 1 The exterior lighting is still unclear per the lighting plan E1.0. Please clarify Delta 1, General Note A refers to Light Fixture Types ‘K1’ and ‘K20’. The plan shows fixtures marked ‘K21’ only. How does all this correlate with the General Note, lighting plans and the Outdoor Lumen Calculations. 2 Why are the interior luminaires associated with this project not identified in the lighting plan? Please identify. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code. |
||
10/07/2024 | PDSD Application Completeness | REVIEW COMPLETED |