Permit Number: TC-COM-0724-01416
Parcel: 12512080A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0724-01416
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2024 Water - PDSD APPROVED
09/18/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/18/2024 External Reviewers - Stantec REQUIRES RESUBMIT August 1, 2024
1st Review

KE Hospitality III, LLC.
Attn: Deborah Tenino
4213 East 6th Street
Tucson, Arizona 85711

Re: MIRAMONTE RESTAURANT
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0724-01416
Stantec Project Number: 185215066
Stantec File Number: TUC-24-101

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-3 V-B 5,621 194 Yes No
Separate Permits: Automatic fire sprinklers and kitchen hood suppression system.
Deferred Submittals: Type I hood and type II hood.
Special Inspections: Epoxy and expansion anchors, structural steel, and field welding.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please indicate that the kitchen hood suppression system [2018 IBC Sec. 904.12] is to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

3. The plans indicate a type I and type II hood. Please either provide the documents now or list on this sheet as a deferred submittal and include the following notes:

PER IBC Section 107.3.4
<Name of Registrant>, the registered design professional in charge shall be responsible for reviewing and coordinating submittal documents prepared by others, including phased and deferred submittal items, for compatibility with the design of the building.

PER IBC Section 107.3.4.1
Submittal documents for deferred submittal items shall be submitted to the registered design professional in responsible charge, who shall review them and forward them to the Building Official with a notation indicating that the deferred submittal documents have been reviewed and that they have been found to be in general conformance with the design of the building.

4. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors, structural steel, and field welding. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet A8

1. Review 2018 IBC Sec. 2902.2 and 2018 IPC Sec. 403.2; separate facilities shall be provided for each sex. Facilities under this code section consist of toilets, urinals, lavatories, and/or showers. The code does not provide for grouped restroom lavatories in one room shared by both sexes. {You could have several family or assisted-use restrooms, with each restroom containing a toilet and lavatory, and supplied with privacy locks or an appeal to the building official to use section 2902.2 exc. 6 of the 2021 IBC for the use of community bathrooms.}

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

Sheet M1

1. Type II hoods shall be installed above dishwashers that produce heat or moisture. Please provide a type II hood over the dishwasher indicated in the dish room. [Ref. IMC 2018 Sec. 507.3]

2. Please indicate the flue vent for the gas fired water heater. [Ref. 2018 IFGC Sec. 503.6]


PLUMBING COMMENTS

Sheet P1

1. Please indicate a trap seal primer for the floor sink in the cooking area. [Ref. IPC 2018 Sec. 1002.4.1]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
08/19/2024 Fire New Construction REQUIRES RESUBMIT -Restaurant should be an A2 classification. Code review on sheet A1 show and A3 occupancy.
john.vincent@tucsonaz.gov
5203495581
08/26/2024 Site Engineering REQUIRES RESUBMIT This project is within a regulated floodplain and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page:
https://tdc-online.tucsonaz.gov/#/home
NOTE: Documentation of a cost estimate from your contractor will be required if this project involves any reconstruction, repair, rehabilitation, structurally connected addition, or other improvement of an existing structure (including TIs and solar). Construction of separate builds/new structures does not require a cost estimate to be provided. Construction of new buildings require elevation one foot above the base flood elevation, which may require that the foundation of the building be raised as much as two feet above the existing elevation onsite. Storage buildings with no utilities may be wet floodproofed using flood vents. For all new construction buildings, two elevation certificates must be filled out by a registered land surveyor and submitted to the City, one before the foundation is poured and one after construction is completed.
Instructions:
1. Navigate into the current project in the “My Work” tab. Within the permit, navigate to the “Sub-Records” tab and click “Apply” on the Floodplain Use Permit Sub-Record
2. Locations -> Confirm the location is accurate to the project. Click “Next”
3. Type -> Fill in the “Square Feet” and “Valuation” boxes with the project area and a contractor-provided cost estimate (See note above: for new structures, input 0). Click “Next”
4. Contacts -> Confirm contacts and add any additional contacts if applicable. Click “Next”
5. More Info -> This will be filled in by the engineer assigned to your case, Click “Next”
6. Attachments -> Please attach the project plan, supporting documentation for the cost estimate (if applicable), and a drainage/hydrology report (if applicable). Click “Next”
7. Signature -> Read the statement and type your name. Sign your name below (You may Enable Type Signature to have the software sign for you.) Click “Next”
8. Review and Submit -> Review all information to ensure accuracy. Click “Submit”

Mike Ortiz
michael.ortiz@tucsonaz.gov
08/19/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: Wyatt Berger
Lead Planner

PROJECT: TC-COM-0724-01416
3352 East Speedway Boulevard – C-3
TI: Food Service (1st Review)

TRANSMITTAL DATE: August 19, 2024

The site is in the C-3 zone (UDC 4.7.22). A Food Service use is permitted in the C-3 zone.

1. Demonstrate that no more than 50% of the gross floor area (gfa) of the shopping center is dedicated to uses with a parking formula of one space per 100 square feet gfa or a more intense formula (UDC 11.3.7.C.3). A development package is required for the proposed change of use if the above requirement is exceeded.

If you have any questions about this transmittal, contact me at Wyatt.Berger@tucsonaz.gov or at 520-837-4951.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: A revised plan set as well as a comment response letter. To resubmit, visit the Tucson Development Center Online at https://tdc-online.tucsonaz.gov/#/home. The instructions for resubmittal can be found at https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf.
07/24/2024 PDSD Application Completeness Express REVIEW COMPLETED