Permit Number: TC-COM-0724-01416
Parcel: 12512080A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0724-01416
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2024 Site Engineering APPROVED
10/28/2024 Site Zoning APPROVED
10/28/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/16/2024 External Reviewers - Stantec REQUIRES RESUBMIT October 15, 2024
2nd Review

KE Hospitality III, LLC.
Attn: Deborah Tenino
4213 East 6th Street
Tucson, Arizona 85711

Re: MIRAMONTE RESTAURANT
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0724-01416
Stantec Project Number: 185215066
Stantec File Number: TUC-24-101

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-3 V-B 5,621 194 Yes No
Separate Permits: Automatic fire sprinklers and kitchen hood suppression system.
Deferred Submittals: Type I hood and type II hood.
Special Inspections: Epoxy and expansion anchors, structural steel, and field welding.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. Addressed.

3. Addressed.

4. Previous Comment: Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors, structural steel, and field welding. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Still Required: The special inspection certification provided is missing special inspection for epoxy anchors. Please revise and resubmit. Further, the special inspection certificate includes masonry and high strength bolting special inspections which are not required as there is no structural masonry or high-strength bolts included in the design. Please remove these special inspections

Sheet A1

1. New Comment: The Occupancy Group indicated for the proposed restaurant is A-3. Please revise to a Group A-2 as Group A-3 includes uses for worship, recreation, or amusement while Group A-2 includes uses food and/or drink consumption. [Ref. IBC 2018 Sec. 303.3]

Sheet A8

1. Addressed.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

Sheet M1

1. Previous Comment: Type II hoods shall be installed above dishwashers that produce heat or moisture. Please provide a type II hood over the dishwasher indicated in the dish room. [Ref. IMC 2018 Sec. 507.3] Still Required: This comment does not appear to be addressed; a type II hood was not included over the indicated dishwasher. A response letter was also not provided for the Mechanical and Plumbing comments to verify reasoning. Please provide a response letter with the next submittal.

2. Addressed.

PLUMBING COMMENTS

Sheet P1

1. Addressed.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
10/22/2024 Fire New Construction REQUIRES RESUBMIT -Restaurant should be an A2 classification. Code review on sheet A1 shows an A3
occupancy.
Questions: patricia.shelton@tucsonaz.gov
10/14/2024 PDSD Application Completeness Express REVIEW COMPLETED