Permit Number: TC-COM-0724-01322
Parcel: 121070160

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0724-01322
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2024 Commercial Electrical APPROVED
08/12/2024 Site Engineering APPROVED
08/07/2024 Site Zoning APPROVED
08/16/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/16/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Sheet M1.0 Provide mechanical compliance certificate for all new equipments to comply with 2018 IECC C403 (BM)
2. Sheet M1.0 DCU A & B are identified on an existing canopy. Verify existing roof structure can support new equipment load. Also identify dimension of equipment to edge of roof. Guards may be required if equipment is less than 10' from edge of roof or if existing parapet is less than 42" above roof surface. 2018 IMC 304.11 (BM)
08/16/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Sheet P0.0 Plan sheet P2.0 is not in plan set for review. Provide missing sheet 2018 IBC 107.2.1 (BM)
2. Sheet P0.0 WHA are required on water supply where quick-closing valves are utilized. Will need to identify at applicable fixtures. 2018 IPC 604.9 (BM)
3. Sheet P0.0 Drinking fountain fixture is identified on plans, drinking fountain is required to be a High and Low type to comply with 2018 IPC 410.3 (BM)
4. Sheet P0.0 Provide on plans a fixture schedule for review. Incomplete 2018 IBC 107.2.1 (BM)
08/16/2024 Commercial Structural REQUIRES RESUBMIT For questions in regards to plan review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179. all applicable comments will be followed by the initials (BM)
1. Sheet A2.0 Key note #9, See comment on plumbing sheet P0.0 for High /low drinking fountain. 2018 IBC 107.2.1 (BM)
2. Sheet S1.0 Provide completed special inspection form for items listed for welding, epoxy and post installed anchors per 2018 IBC 1705. (BM)
3. Sheet S1.0 Provide calculations for new metal canopy structure for review, 2018 IBC 107.2.1 (BM)
4. Sheet S2.0 New wall type is not identified, Clarify 2018 IBC107.2.1 (BM)
08/08/2024 Fire New Construction REQUIRES RESUBMIT -Sheet A1.0, Deferred submittals. Remove "northwest fire district." This is in the city of Tucson and is the Tucson Fire Department, not NWFD. The referenced code for the fire alarm in the deferred submittal explanation is incorrect. Please contact to discuss this reference and the fire sprinkler/fire alarm requirements.
john.vincent@tucsonaz.gov
5203495581
07/11/2024 PDSD Application Completeness Express REVIEW COMPLETED