Review Details: COMMERCIAL REVIEW - FULL REVISION v.2
Permit Number - TC-COM-0724-01311
Review Name: COMMERCIAL REVIEW - FULL REVISION v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2025 | Commercial Building Standard | APPROVED | Structural(S) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 5/21/2025 10:52:45 AM Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 5/21/2025 10:52:40 AM |
||
| 05/21/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/21/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Denied Reason: Date Completed : 5/21/2025 9:19:14 AM 1. E5.1: Shall provide a Short Circuit calculation as required by Tucson. Shall call out a KAIC rating for the Temporary Service. 2. E5.1: Shall provide an estimated load calculation to show panel provided is adequately sized. 3. E5.1: Should provide a prospective panel schedule to call out for a selection of usable circuit breakers (or call out in notes that the contractor is to provide as required by equipment). 4. E5.1: Comment only, should consider calling out for a 3 phase temporary service. This would support larger 3 phase motors that may be required for some construction equipment ie lifts, elevators, etc. |
||