Permit Number: TC-COM-0724-01311
Parcel: 141185450

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.2

Permit Number - TC-COM-0724-01311
Review Name: COMMERCIAL REVIEW - FULL REVISION v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2025 Commercial Building Standard APPROVED Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/21/2025 10:52:45 AM


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/21/2025 10:52:40 AM
05/21/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/21/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 5/21/2025 9:19:14 AM
1. E5.1: Shall provide a Short Circuit calculation as required by Tucson. Shall call out a KAIC rating for the Temporary Service.
2. E5.1: Shall provide an estimated load calculation to show panel provided is adequately sized.
3. E5.1: Should provide a prospective panel schedule to call out for a selection of usable circuit breakers (or call out in notes that the contractor is to provide as required by equipment).
4. E5.1: Comment only, should consider calling out for a 3 phase temporary service. This would support larger 3 phase motors that may be required for some construction equipment ie lifts, elevators, etc.