Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0724-01284
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2024 Site Engineering APPROVED
07/31/2024 Site Zoning APPROVED
08/05/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
07/23/2024 External Reviewers - Stantec REQUIRES RESUBMIT July 15, 2024
1st Review

Joseph Maher Jr., Architect
Attn: Joseph Maher
4849 E. Scarlett Street
Tucson, Arizona 85711

Re: SPANISH TRAIL CONDOS – UNIT 113
REPAIR

City of Tucson Permit Number: TC-COM-0724-01284
Stantec Project Number: 185215066
Stantec File Number: TUC-24-089

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural and structural designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-2 V-B 958 5 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: Concrete and epoxy and expansion anchors.

ARCHITECTURAL COMMENTS

General

1. Note on the cover of the drawings that special inspection is required for concrete and epoxy and expansion anchors. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

2. The architectural plans indicate marks at the doors with no schedule or description. Please clarify.

Sheet BDX-1

1. The extent of demolition is not indicated nor described on this sheet as referenced by the sheet name on the sheet index. Please revise.

Sheet BAN-1

1. The extent of remodel is not indicated nor described on this sheet as referenced by the sheet name on the sheet index. Please revise.

STRUCTURAL COMMENTS

Sheet S1.0

1. Note 12 on this sheet indicates no special inspections are required. The structural plans indicate the use of epoxy set anchors and a concrete strength design of 3,000psi which requires special inspections per Section 1705.3 of the 2018 International Building Code. Please indicate these special inspections.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
08/01/2024 Fire New Construction REVIEW COMPLETED
07/03/2024 PDSD Application Completeness REVIEW COMPLETED