Permit Number: TC-COM-0723-01867
Parcel: 11515214B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0723-01867
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/05/2023 Water - PDSD APPROVED MASTER SET LOCATED AT: TC-COM-0723-01867/BLDG 1 Studio Session 694-204-313 WITH REVIEW NOTES TO BE COMPLETED ON TC-COM-0723-01868 (785 W SAHUARO ST Unit:BLDG 5 TUCSON, AZ 85705)
08/15/2023 Site Engineering NOT REQUIRED
08/16/2023 Site Zoning NOT REQUIRED
09/05/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT MASTER SET LOCATED AT: TC-COM-0723-01867/BLDG 1 Studio Session 694-204-313 WITH REVIEW NOTES TO BE COMPLETED ON TC-COM-0723-01868 (785 W SAHUARO ST Unit:BLDG 5 TUCSON, AZ 85705)
09/01/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 9/1/2023 12:18:39 PM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 9/1/2023 12:15:39 PM
1) General: Provide the geotechnical engineer report that is referenced on sheets S100 and S102. (2018 IBC section 1803)

2) Sheets G102, A102, and A901 (Toilet Room Accessibility Drawings): Show the turning space in the men's toilet room per 2009 ICC A117.1 sections 304.3.1 and 603.2.

3) Sheet P301 (Plumbing Calculations): Include the minimum plumbing fixture calculations based on the occupancy loads of the buildings that the toilet rooms are serving and meeting the requirements of 2018 IBC Table 1004.5 and 2018 IPC section 403 and Table 403.1. Revise all applicable pages as needed for toilet room fixtures and drinking fountains.

4) Sheet P301 (Plumbing Details): Include the details for how the water supply piping is being protected from freezing. (2018 IPC section P305.4)

5) Sheet P301 (Plumbing Details): Provide the faucet details showing compliance with the automatic faucet requirements of the amended 2018 IPC sections 412.11 and 419.6.

6) Sheet A901 details 3 and 13 (Toilet room Elevations): The urinal partitions are not shown being a minimum of 60" above the floor. (2018 IPC section 405.3.5 and 2018 IBC section 1209.3.2)



Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 9/1/2023 12:17:20 PM
See the building review comments. No mechanical revisions are needed at this time.



Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 9/1/2023 12:16:52 PM
See the building review comments. No electrical revisions are needed at this time.



Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 9/1/2023 12:18:13 PM
See the building review comments
08/16/2023 Fire New Construction REVIEW COMPLETED
08/15/2023 PDSD Application Completeness Express REVIEW COMPLETED